Table 7c.

 North American Overpressure and Underpressure Shut-off UPSO/OPSO Ranges

Table 7d.

 European Overpressure and Underpressure Shut-off UPSO/OPSO Ranges

Example:

 

If a non-standard setpoint is needed, see the following example for the proper use of Tables 7a, 7b, 7c and 7d. In this 

example, the non-standard regulator setpoint is 140 mbar / 2.0 psig. The minimum factory token relief set pressure is 130% of the 

non-standard setpoint. The resulting token relief set pressure is 183 mbar / 2.6 psig. The minimum factory OPSO and UPSO set 

pressures are 165% and 50% of the non-standard setpoint, respectively. The resulting minimum settings are: OPSO = 231 mbar / 

3.4 psig and UPSO = 70 mbar / 1.0 psig.

REGULATOR

SLAM SHUT DEVICE

Type

Typical 

Setpoint

Spring 

Range

Type 

(Maximum 

Operating 

Inlet)

Token 

Relief Set

Relief Range Shown 

as a % of Regulator 

Setpoint

Required 

Difference 

Between Token 

Relief and 

OPSO

UPSO

OPSO

Factory Set

Set Range

Shut-off (OPSO) 

Set Range Over 

UPSO Setpoint

UPSO

Adjusted 

OPSO Range OPSO

mbar

mbar

mbar

min

max

mbar

mbar

mbar

mbar

mbar

mbar

CSB704F

15

13 to 24

VSX8L (8.6 bar)

26 

170 

215 

6

7 to 11

30 to 44

8

38 to 52

40

20

13 to 24

34 

170 

215 

6

7 to 11

30 to 44

10

40 to 54

40

21

13 to 24

36 

170 

215 

7 to 11

30 to 44

10

40 to 54

40 

27

22 to 39

41 

150 

160 

5

7 to 15

32 to 44

14

46 to 58

46 

30

22 to 39

45 

150 

160 

10 

7 to 30

40 to 72

15

55 to 87

60 

35

22 to 39

53 

150 

160 

10 

7 to 30

40 to 72

18

58 to 90

70 

50

42 to 70

70 

140 

158 

16 

10 to 75

48 to 74

25

73 to 99

90

60

84 

140 

158 

16 

48 to 74

30

78 to 104

100

75

61 to 110

98 

130 

140 

20 

25 to 160

83 to 221

38

121 to 259

130 

CSB704

15

13 to 24

VSX8L (16 bar)

26 

170 

215 

7 to 30

40 to 55

8

48 to 63

50

20

13 to 24

34 

170 

215 

7 to 30

40 to 55

10

50 to 65

55

21

13 to 24

36 

170 

215 

7 to 30

40 to 55

10

50 to 65

55

27

22 to 39

41 

150 

160 

7 to 30

40 to 55

14

54 to 69

55

30

45 

150 

160 

10 

7 to 30

45 to 76

15

60 to 91

60

35

53 

150 

160 

10 

7 to 30

45 to 76

18

63 to 94

70

50

42 to 70

70 

140 

158 

16 

10 to 75

50 to 80

25

75 to 105

90

60

84 

140 

158 

16 

50 to 80

30

80 to 110

100

75

61 to 110

98 

130 

140 

20 

25 to 160

83 to 221

38

121 to 259

130

CSB724

100 

130 

130 

140 

20 

50 

133 to 271

170 

120 

105 to 220

156 

130 

140 

40 

60 

143 to 281

205 

150 

195 

130 

140 

40 

75 

158 to 296

250 

160 

208 

130 

140 

40 

25 to 160

83 to 221

80 

163 to 301

265 

200 

250 

125 

140 

50 

100 to 500

114 to 261

100 

214 to 361

330 

300 

210 to 380

375 

125 

140 

50 

179 to 386

150 

329 to 536

450 

500 

320 to 570

625 

125 

140 

60 

241 to 565

250 

491 to 815

700 

600 

510 to 780

100 to 500

241 to 565

300 

541 to 865

840 

750 

100 to 750

460 to 932

375 

835 to 1120

(1)

1050 

CSB724F

300 

270 to 325

VSX8L (8.6 bar)

100 to 500

179 to 386

200 

379 to 586

400 

CSB754 GrDF

1 bar

0.7 to  

1.19 bar

VSX8L (16 bar)

100 to 500

460 to 932

750 

1210 to 1682

1210 

CSB754

1 bar

0.7 to  

1.19 bar

100 to 500

460 to 932

500 

960 to 1432

1320 

1.2 bar

1.05 to  

2.7 bar

VSX8H (16 bar)

500 to 2000

1050 to 1570

600 

1650 to 2170

1650 

1.5 bar

750 

1800 to 2320

1900 

2 bar

1250 to 2300

1000 

2250 to 3300

2400 

3 bar

2.3 to  

3.25 bar

1500 

2750 to 3800

3400 

4 bar

3.1 to 4 bar

500 to 2800

2100 to 3750

2000

4100 to 5000

(1)

4400

 - Gray areas indicate that token relief is not available above 500 mbar setpoint.

1. Max OPSO setpoint truncated to reflect maximum outlet pressure for spring range.

REGULATOR

SLAM SHUT DEVICE

Type

Typical 

Setpoint

Spring Range

Type 

(Maximum 

Operating 

Inlet)

Token 

Relief Set

Relief Range Shown 

as a % of Regulator 

Setpoint

Required 

Difference 

Between 

Token 

Relief and 

OPSO

UPSO

OPSO

Factory Set

Set Range

Shut-off (OPSO) 

Set Range Over 

UPSO Setpoint

UPSO

Adjusted 

OPSO 

Range

OPSO

psig

psig

psig

min

max

psig

psig

psig

psig

psig

psig

CSB704F

7 in. w.c.

5.2 to 9.6 in. w.c.

VSX8L

(125 psi)

12 in. w.c.

170

215

3.2 in. w.c.

3 to 12 in. w.c.

16 to 29 in. w.c.

3 in. w.c.

19 in. w.c. 

to 1.2 psig

22 in. w.c.

11 in. w.c.

8.8 to 15.7 in. w.c.

17 in. w.c.

150

160

4 in. w.c.

6 in. w.c.

22 in. w.c. 

to 1.3 psig

25 in. w.c.

14 in. w.c.

12.8 to 20.0 in. w.c.

21 in. wc

150

160

4 in. w.c.

4 in. w.c. to 

1.1 psig

20 in. w.c. to 

1.8 psig

9 in. w.c.

1 to  

2.1 psig

1.1

1

24.0 in. w.c. to 1.6 psig

1.4

140

150

6.4 in. w.c.

10 in. w.c. to 

2.3 psig

1.2 to 3.2

14 in. w.c.

1.7 to 3.7

2

CSB724

2

1.5 to 3.2

2.6

130

140

0.6

1

2.2 to 4.2

3.5

3

3.8

125

140

0.6

1.5 to 7.3

2.6 to 5.6

2

4.6 to 7.6

5

5

3.1 to 5.5

6.2

125

140

0.7

1.5 to 7.3

3.5 to 8.2

3

5.6 to 8.6

7

10

7.4 to 11.3

1.5 to 7.3

3.5 to 8.2

5

8.5 to 13.2

12

CSB704

7 in. w.c.

5.2 to 9.6 in. w.c.

VSX8L

(232 psi)

12 in. w.c.

170

215

3.2 in. w.c.

3 to 12 in. w.c.

18 to 30 in. w.c.

3 in. w.c.

21 in. w.c. 

to 1.2 psig

22 in. w.c.

11 in. w.c.

8.8 to 15.7 in. w.c.

17 in. w.c.

150

160

4 in. w.c.

6 in. w.c.

24 in. w.c. 

to 1.3 psig

25 in. w.c.

14 in. w.c.

12.8 to 20.0 in. w.c.

21 in. w.c.

150

160

4 in. w.c.

4 in. w.c. to 

1.1 psig

25 in. w.c. to  

1.9 psig

9 in. w.c.

1.2 to 2.2

1.1

1

24.0 in. w.c. to 1.6 psig

1.4

140

150

6.4 in. w.c.

10 in. w.c. to 

2.3 psig

1.2 to 3.2

14 in. w.c.

1.7 to 3.7

2

CSB724

2

1.5 to 3.2

2.6

130

140

0.6

1

2.2 to 4.2

3.5

3

3.8

125

140

0.6

1.5 to 7.3

2.6 to 5.6

2

4.6 to 7.6

5

5

3.1 to 5.5

6.2

125

140

0.7

3

5.6 to 8.6

7

10

7.4 to 11.3

3.5 to 8.2

5

8.5 to 13.2

12

CSB754

15

10.2 to 17.3

1.5 to 10.9

6.7 to 13.5

7

13.7 to 20.5

19

20

15.2 to 39.2

VSX8H

(232 psi)

7.3 to 29.0

15.2 to 22.8 

10

25.2 to 32.8

25

30

18.1 to 33.4

15

33.1 to 48.4

35

40

33.4 to 55.1

20

38.1 to 53.4

45

 - Gray areas indicate that token relief is not available above 8 psig setpoint.

Summary of Contents for CSB700 Series

Page 1: ...tions and Pressure Ratings 1 See Table 4 Operating Pressure Range 1 Regulator See Table 5 Slam Shut Module See Tables 7a 7b 7c and 7d Maximum Outlet Pressure 1 Emergency Casing Type CSB700 CSB700F CSB720 CSB720F 4 0 bar 58 0 psig Type CSB750 5 0 bar 72 5 psig To Avoid Internal Metallic Parts Damage Type CSB700 CSB700F CSB720 CSB720F 0 34 bar 5 0 psig over set pressure Type CSB750 1 5 bar 21 8 psig...

Page 2: ...regarding the Type VSX8 Slam shut Module 2 The pressure temperature limits in this Installation Guide and any applicable standard or code limitation should not be exceeded 3 Token relief not available for outlet pressure above 500 mbar 8 psig TYPE MAXIMUM ALLOWABLE PRESSURE MAXIMUM EMERGENCY INLET PRESSURE MAXIMUM OPERATING INLET PRESSURE 2 PS PUMAX bar psig bar psig CSB700 and CSB704 4 0 58 0 4 0...

Page 3: ...URE RANGES Wd PART NUMBER SPRING COLOR SPRING WIRE DIAMETER SPRING FREE LENGTH mbar psig mm In mm In CSB700 CSB704 CSB700F and CSB704F 9 to 14 3 6 to 5 6 in w c GE30336X012 Silver 3 00 0 118 224 8 82 13 to 24 5 2 to 9 6 in w c ERSA01138A0 Red 3 50 0 138 264 10 4 22 to 39 8 8 to 15 7 in w c GE30338X012 Black Stripe 4 32 0 170 172 6 78 32 to 50 12 8 to 20 1 in w c GE30339X012 Purple 4 34 0 171 187 7...

Page 4: ...50 1600 to 5000 1 3400 4000 3100 to 4000 4400 Gray areas indicate that token relief is not available above 500 mbar setpoint 1 Max OPSO setpoint truncated to reflect maximum outlet pressure for spring range Table 7a North American Overpressure Shut off OPSO Only Ranges REGULATOR SLAM SHUT DEVICE Type Typical Setpoint Spring Range Type Maximum Operating Inlet Token Relief Set Relief Range Shown as ...

Page 5: ... 750 460 to 932 375 835 to 1120 1 1050 CSB724F 300 270 to 325 VSX8L 8 6 bar 100 to 500 179 to 386 200 379 to 586 400 CSB754 GrDF 1 bar 0 7 to 1 19 bar VSX8L 16 bar 100 to 500 460 to 932 750 1210 to 1682 1210 CSB754 1 bar 0 7 to 1 19 bar 100 to 500 460 to 932 500 960 to 1432 1320 1 2 bar 1 05 to 2 7 bar VSX8H 16 bar 500 to 2000 1050 to 1570 600 1650 to 2170 1650 1 5 bar 750 1800 to 2320 1900 2 bar ...

Page 6: ... in w c outlet pressure For pressure greater than this set the Type 289H 0 05 bar 0 73 psi higher than the outlet pressure setting of the regulator Refer to the 289 Series Instruction Manual D100280X012 for more information Installation WARNING Only qualified personnel shall install or service a regulator Regulators should be installed operated and maintained in accordance with international and a...

Page 7: ...tlet pressure rating Overpressure protection should also be provided if the regulator inlet pressure is greater than the safe working pressure of the downstream equipment Regulator operation below the maximum pressure limitations does not preclude the possibility of damage from external sources or debris in the line The regulator should be inspected for damage after any overpressure condition Star...

Page 8: ...alve Seat Nut Zinc plated steel 41 Token Relief Spring Music Wire 42 Spring Retainer Zinc plated steel with token relief 43 Spring Seat Zinc plated steel 44 Stem Zinc plated steel with token relief Recommended spare part Lustran is a mark owned by INEOS ABS USA Limited 45 Screw Zinc plated steel without token relief 46 Token Relief Nut Steel 50 Pusher Post Aluminum 51 Relief Valve Seat Aluminum 52...

Page 9: ...ator Installed with the Vent Pointed Downward and with a Type 289H Relief Valve for High Capacity Relief CSB700 SERIES REGULATOR PROTECT VENT PIPE WITH RAIN CAP DN 50 NPS 2 TYPE 289H RELIEF VALVE Note Install with vent pointed vertically down Otherwise regulator must be installed under a separate protective cover ...

Page 10: ...RQUE 6 TO 8 N m 4 TO 6 FT LBS 111C 111D 111B 111F L1 25 L2 82 L2 36 71 80 20 21 L2 L2 L1 65 62 L1 L2 100 8 TORQUE 1 7 TO 3 4 N m 15 TO 30 IN LBS 95 6 111E 111A TORQUE 10 TO 13 N m 7 TO 10 FT LBS 111G 43 55 9 1 4 7 5 TORQUE 1 7 TO 3 4 N m 15 TO 30 IN LBS 51 44 52 TORQUE 6 TO 7 N m 50 TO 60 IN LBS L2 50 54 53 68 112 13 14 10 TORQUE 3 5 TO 4 N m 31 TO 35 IN LBS 18 17 11 L2 76 77 75 19 96 74 L2 L2 L2 ...

Page 11: ...1C 111G 111D 111B 111E 55 1 9 43 105 TORQUE 10 TO 13 N m 7 TO 10 FT LBS L2 53 19 L2 75 L2 54 L2 77 76 74 96 10 14 13 112 11 18 68 TORQUE 3 5 TO 4 N m 31 TO 35 IN LBS L2 L2 82 L1 25 TORQUE 34 TO 47 N m 25 TO 35 FT LBS 80 TORQUE 6 TO 8 N m 4 TO 6 FT LBS TORQUE 6 TO 7 N m 50 TO 60 IN LBS TORQUE 12 N m 9 FT LBS MAX 51 45 40 L1 38 63 66 36 71 TORQUE 14 TO 18 N m 10 TO 13 FT LBS 70 17 16 15 INITIAL TORQ...

Page 12: ...rson Automation Solutions D103483X014 2017 2018 Emerson Process Management Regulator Technologies Inc All rights reserved 07 18 The Emerson logo is a trademark and service mark of Emerson Electric Co All other marks are the property of their prospective owners Fisher is a mark owned by Fisher Controls International LLC a business of Emerson Automation Solutions The contents of this publication are...

Reviews: