15
Electrical Connection
Power Supply
The ZX condensing unit electrical connection to the power supply must be made by qualified technicians, who should refer to the
electrical diagrams located inside the electric connection panel. The units are designed for below power supply at ± 10% voltage
tolerance. The circuit breaker must be switched off before opening the front panel.
Electrical Wiring
Before commissioning, ensure that neutral “N” wire is connected to the terminal block (“N” furthest to the right). After proper
connection of the ZX condensing unit, the control LED on the power board and control board will light up. For more details, see wiring
diagrams. Customers’ wire size needs to be selected to allow for the maximum operation current of each unit.
BOM
Codes
HZ
Phase
Voltages
ALL
PFJ
50
1
220/240
ALL
TFD
50
3
380/420
ALL
TF7
60
3
380
401/451
TF5
60
3
230
471
TF5
60
3
200
Caution!
Unit should be powered on at all times except during service. Failure to do so can result in component failure.
Unit
Unit MOC (A)
ZX020BE-TFD
5.7
ZX030BE-TFD
8.0
ZX040BE-TFD
11.1
ZX050BE-TFD
14.4
ZX060BE-TFD
14.7
ZX075BE-TFD
15.6
ZX076BE-TFD
15.6
ZX020B0-TFD
5.3
ZX030B0-TFD
8.8
ZX040B0-TFD
9.8
ZX050B0-TFD
13.6
ZX060B0-TFD
14.7
ZX075B0-TFD
15.6
ZX076B0-TFD
15.6
ZX020BE-TF5
11.3
ZX030BE-TF5
15.4
ZX040BE-TF5
20.7
ZX050BE-TF5
24.6
ZX060BE-TF5
28.7
ZX075BE-TF5
27.4
ZX020B0-TF5
11.3
ZX030B0-TF5
15.4
ZX040B0-TF5
20.7
ZX050B0-TF5
24.6
ZX060B0-TF5
28.7
ZX075B0-TF5
27.4
ZX020BE-TF7
8.3
ZX030BE-TF7
8.3
ZX040BE-TF7
12.2
ZX050BE-TF7
15.2
ZX060BE-TF7
15.3
ZX075BE-TF7
17.2
ZX020B0-TF7
8.3
ZX030B0-TF7
8.3
ZX040B0-TF7
12.2
ZX050B0-TF7
15.2
ZX060B0-TF7
15.3
ZX075B0-TF7
17.2
ZX020BE-PFJ
13.6
ZX025BE-PFJ
13.2
ZX030BE-PFJ
17.2
ZX040BE-PFJ
24.3
ZX020B0-PFJ
13.6
ZX025B0-PFJ
13.2
ZX030B0-PFJ
17.2
ZX040B0-PFJ
24.3
Unit
Unit MOC (A)
ZXL020BE-TFD
6.5
ZXL025BE-TFD
6.9
ZXL030BE-TFD
7.5
ZXL035BE-TFD
8.3
ZXL040BE-TFD
10.0
ZXL050BE-TFD
13.5
ZXL060BE-TFD
15.3
ZXL075BE-TFD
16.2
ZXL020B0-TFD
6.0
ZXL025B0-TFD
6.4
ZXL030B0-TFD
7.0
ZXL035B0-TFD
7.4
ZXL040B0-TFD
9.0
ZXL050B0-TFD
11.7
ZXL060B0-TFD
12.8
ZXL075B0-TFD
15.2
ZXL020BE-TF5
12.4
ZXL025BE-TF5
13.5
ZXL030BE-TF5
15.5
ZXL035BE-TF5
15.7
ZXL040BE-TF5
23.2
ZXL050BE-TF5
25.7
ZXL060BE-TF5
31.2
ZXL075BE-TF5
33.4
ZXL020B0-TF5
10.9
ZXL025B0-TF5
12.0
ZXL030B0-TF5
14.0
ZXL035B0-TF5
15.5
ZXL040B0-TF5
20.0
ZXL050B0-TF5
22.6
ZXL060B0-TF5
27.4
ZXL075B0-TF5
33.2
ZXL020BE-TF7
7.3
ZXL025BE-TF7
7.2
ZXL030BE-TF7
8.4
ZXL035BE-TF7
9.7
ZXL040BE-TF7
12.7
ZXL050BE-TF7
14.8
ZXL060BE-TF7
18.1
ZXL075BE-TF7
18.6
ZXL020B0-TF7
6.5
ZXL025B0-TF7
6.7
ZXL030B0-TF7
7.7
ZXL035B0-TF7
9.1
ZXL040B0-TF7
11.9
ZXL050B0-TF7
13.2
ZXL060B0-TF7
16.4
ZXL075B0-TF7
17.1
Unit
Unit MOC (A)
ZXD040BE-TFD
9.5
ZXD050BE-TFD
12.9
ZXD060BE-TFD
13.0
ZXD075BE-TFD
15.6
ZXD076BE-TFD
15.6
ZXD040B0-TFD
11.6
ZXD050B0-TFD
14.4
ZXD060B0-TFD
14.1
ZXD075B0-TFD
16.8
ZXD076B0-TFD
16.8
ZXD040BE-TF7
11.5
ZXD050BE-TF7
14.2
ZXD060BE-TF7
16.2
ZXD075BE-TF7
17.6
ZXD040B0-TF7
12.2
ZXD050B0-TF7
15.0
ZXD060B0-TF7
15.8
ZXD075B0-TF7
20.3
ZXB015BE-TFD
6.5
ZXB020BE-TFD
6.9
ZXB025BE-TFD
7.5
ZXB030BE-TFD
8.3
ZXB035BE-TFD
10.0
ZXB040BE-TFD
13.5
ZXB050BE-TFD
15.3
ZXB060BE-TFD
16.2