background image

 

 

Application Engineering  

B  U  L  L  E  T  I  N 

AE4-1374 R1 

 

To  avoid  disruption  of  operation,  an  electronic  control 
that  can  sense  brief  power  interruptions  may  be  used 
to lock out the compressor for a short time. This control 
could  be  incorporated  in  other  system  controls  (such 
as  defrost  control  board  or  the  system  thermostat),  or 
can  be  a  stand-alone  control.  Functional  specifications 
for  this  control  as  well  as  a  suggested  wiring  diagram 
are  shown  in  Figure  3.  No  time  delay  is  necessary  for 
three  phase  models  since  the  motor  starting  torque  is 
high enough to overcome reverse rotation. 

APPLICATION TESTS  

Application Test Summary 

There  are  a  minimal  number  of  tests  the  system  
designer will want to run to ensure the system operates  
as  designed.  These  tests  should  be  performed  during  
system  development  and  are  dependent  on  the  system  
type  and  amount  of  refrigerant  charge.  These  application  
tests  are  to  help  identify  gross  errors  in  system  design  that  
may  produce  conditions  that  could  lead  to  compressor  
failure.  The  Continuous  Floodback  Test  and  Field  
Application  Test,  both  outlined  below,  are  two  tests  to  
run  to  help  verify  the  design. When  to  run  these  tests  
can be summarized as follows: 

Continuous Floodback: 

Required on all air-source heatpumps. 

Field Application Test: 

Required for any unit where both the design system 
charge  is  higher  than  the  compressor  refrigerant 
charge  limit  listed  in  Table  4;  and  a  capillary  tube, 
fixed  orifice,  or  bleed-type  TXV  is  used  on  either 
the indoor or the outdoor coil of the unit. 

Continuous Floodback Test 

It  is  expected  that  the  design  would  not  flood  during  
standard  air  conditioning  operation.  Running  a  partially  
blocked  indoor  air filter  or  loss  of  evaporator  air flow  test  
and comparing the sump temperature results to Figure 
1  is  recommended.  The  use  of  a  TXV  in  heating  does 
not  guarantee  operation  without  flood  back  in  the  lower 
end of the unit/TXV operating range. 

To  test  for  excessive  continuous  liquid  refrigerant  flood  
back,  it  is  necessary  to  operate  the  system  in  a  test  
room  at  conditions  where  steady  state  flood  back  may  
occur  (low  ambient  heating  operation).  Thermocouples  
should be  attached  with glue or solder to the center of  
the bottom shell and to the  suction and discharge lines  
approximately  6  inches  (15  cm)  from  the  shell.  These  
thermocouples  should  be  insulated  from  the  ambient  air  
with  Permagum®  or  other  thermal  insulation  to  be  able  
to record true shell and line temperatures. If the system  
is designed to be field charged, it should be overcharged 

 

 

 

 

©  2013  Emerson  Climate  Technologies,  Inc. 
Printed in the U.S.A. 

 

by 15% in this test to simulate overcharging often found 
in field installations. 

The system should be operated at an indoor temperature  
of  70°F  (21°C)  and  outdoor  temperature  extremes  of  
10°F  (-12°C)  or  lower  in  heating  to  produce flood  back  
conditions.  The  compressor  suction  and  discharge  
pressures  and  temperatures  as  well  as  the  sump  
temperature  should  be  recorded.  The  system  should  
be  allowed  to frost  up for several  hours  (disabling the  
defrost  control  and spraying  water  on  the  outdoor coil  
may  be  necessary)  to  cause  the  saturated  suction  
temperature  to fall  below  0°F  (-18°C). The compressor  
sump  temperature  must  remain  above  the  sump  
temperature  shown  in  Figure  1  or  design  changes  
must be made to reduce the amount of flood back. If an  
accumulator is used, this test can be used to test the  
effectiveness  of  the  accumulator.  Increasing  indoor  coil  
volume,  increasing  outdoor  air  flow,  reducing  refrigerant  
charge,  decreasing  capillary  or  orifice  diameter,  and  
adding a charge compensator can also be used to reduce  
excessive continuous liquid refrigerant flood back. 

Field Application Test 

To  test  for  repeated,  excessive  liquid  flood  back  during 
normal  system  off-cycles,  perform  the  Field  Application 
Test  that  is  outlined  in  Table  1.  Obtain  a  sample 
compressor with a sight-tube to measure the liquid level 
in the compressor when it is off. 

Note: The sight-tube is not a good liquid level indicator 
when the compressor is running because the top of the 
sight-tube is at a lower pressure than the bottom causing a 
higher apparent oil level. 

Set  the  system  up  in  a  configuration  with  the  indoor  
unit  elevated  several  feet  above  the  outdoor  unit  with  
a minimum  of  25 feet (8 meters)  of connecting  tubing  
with no traps between the indoor and outdoor units. If  
the system is designed to be field charged, the system  
should  be overcharged by  15%  in this test  to simulate  
field  overcharging.  Operate  the  system  in  the  cooling  
mode  at the  outdoor  ambient,  on/off  cycle  times,  and  
number of cycles specified in Table 1. Record the height  
of the liquid in the compressor at the start of each on  
cycle, any compressor overload trips, or any compressor  
abnormal  starting  sounds  during  each  test.  Review  
the  results  with  Application  Engineering  to  determine  
if an accumulator or other means of off cycle migration  
control  are  required.  This  test  does  not  eliminate  the  
requirement  for  a  crankcase  heater  if  the  system  
charge  level  exceeds  the  values  in  Table  4.  The  
criteria  for  pass/fail  is  whether  the  liquid  level  reaches  
the  suction  tube  level.  Liquid  levels  higher  than  this  can  
allow  refrigerant/oil  to  be  ingested  by  the  scrolls  and  
pumped out of the compressor after start-up. 

 
 

11  

Summary of Contents for Copeland ZR16

Page 1: ...ning System Suction Line Noise and Vibration 9 Mounting Parts 9 Single Phase Starting Characteristics 9 PTC Start Components 9 Electrical Connections 9 Deep Vacuum Operation 10 Shell Temperature 10 2013 Emerson Climate Technologies Inc 1 Printed in the U S A System Tubing Stress 10 Three Phase Scroll Electrical Phasing 10 Brief Power Interruptions 10 Application Tests Application Test Summary 11 C...

Page 2: ...to follow these safety instructions SafetyIconExplanation DANGER WARNING CAUTION NOTICE CAUTION 2013 Emerson Climate Technologies Inc Printed in the U S A DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol ind...

Page 3: ...tem Use only approved refrigerants and refrigeration oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Personal safety equipment must be u...

Page 4: ...ll depend on the type of refrigerant metering device Fixed orifice devices may flood the compressor with refrigerant and thermostatic expansion devices will attempt to control superheat and result in higher compressor top cap temperatures Fan failure testing or loss of air flow in both cooling and heating should be evaluated by the system designer to assure that the compressor and system are prote...

Page 5: ...A higher level of protection is achieved if the low pressure control is set to cut out around 55 psig 3 8 bar to prevent evaporator coil icing The cut in setting can be as high as 105 psig 7 2 bar to prevent rapid recycling in case of refrigerant loss If an 2013 Emerson Climate Technologies Inc Printed in the U S A electronic controller is used the system can be locked out after repeated low press...

Page 6: ... prevent liquid slugging and subsequent oil pump out at the beginning and end of the defrost cycle should be assessed during system development This will require special accumulators and compressors with 2013 Emerson Climate Technologies Inc Printed in the U S A sight tubes and or sight glasses for monitoring refrigerant and oil levels Charge Compensators Charge compensators are devices that store...

Page 7: ...siderations in the section on Brief Power 2013 Emerson Climate Technologies Inc Printed in the U S A Interruptions there is no minimum off time because Copeland Scroll compressors start unloaded even if the system has unbalanced pressures The most critical consideration is the minimum run time required to return oil to the compressor after startup To establish the minimum run time obtain a sample ...

Page 8: ...ystem manufacturing processes that leave solid or liquid contaminants in the evaporator coil condenser coil and interconnecting tubing plus any contaminants introduced during the field installation process Molecular sieve and activated alumina are two filter drier materials designed to remove moisture and mitigate acid formation A 100 molecular sieve filter can be used for maximum moisture capacit...

Page 9: ... sound phenomena described above are not usually associated with heat pump systems because of the isolation and attenuation provided by the reversing valve and tubing bends 2013 Emerson Climate Technologies Inc Printed in the U S A Mounting Parts Table 3 lists the mounting parts to be used with these compressors Many OEM customers buy the mounting parts directly from the supplier but Emerson s gro...

Page 10: ... other types of compressors will only compress in one rotational direction Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction except as described in the section Brief Power Interruptions Three phase compressors will rotate in either direction depending upon phasing of the power Since there is a 50 chance of connecting po...

Page 11: ...013 Emerson Climate Technologies Inc Printed in the U S A by 15 in this test to simulate overcharging often found in field installations The system should be operated at an indoor temperature of 70 F 21 C and outdoor temperature extremes of 10 F 12 C or lower in heating to produce flood back conditions The compressor suction and discharge pressures and temperatures as well as the sump temperature ...

Page 12: ...ge the compressor resulting in failure 2013 Emerson Climate Technologies Inc Printed in the U S A Pressure Testing WARNING Never pressurize the compressor to more than 350 psig 24 bar for leak checking purposes Never pressurize the compressor from a nitrogen cylinder or other pressure source without an appropriately sized pressure regulating and relief valve The pressure used on the line to meet t...

Page 13: ...ing a compressor and applying the highest nameplate voltage to the motor The amperage that the motor draws after four seconds is the value that is used on the nameplate Since there is a direct ratio between voltage and locked rotor amperage the lower the line voltage used to start the compressor the lower the locked rotor amperage will be 2013 Emerson Climate Technologies Inc Printed in the U S A ...

Page 14: ...base 2013 Emerson Climate Technologies Inc Printed in the U S A Compressor Replacement After a Motor Burn In the case of a motor burn the majority of contaminated oil will be removed with the compressor The rest of the oil is cleaned with the use of suction and liquid line filter driers A 100 activated alumina suction filter drier is recommended but must be removed after 72 hours See AE24 1105 for...

Page 15: ...30 Unacceptable 4 20 Too Much Refrigerant Dilu on 10 14 0 10 24 20 10 0 10 20 30 40 50 Evapora ng Temperature F Note 1 Operation in this refrigerant dilution area is safe in air to air heat pump heating mode For other applications such as AC only review expansion device to raise superheat A cold sump may result in high refrigerant migration after shut down Figure 1 Oil Dilution Chart 2013 Emerson ...

Page 16: ...harge is over the charge limit shown in Table 5 a crankcase heater is required Figure 2 Accumulator Piping Line Voltage Fuse A B Typical Solid State Timer if used Discharge Line System Operating Thermostat Time Delay Relay Specifications Timer Opens 1 Electrical Cycle Thermostat if used Compressor Contactor C Other Protective Devices if used Timer Closes Greater than 5 seconds later whether 016 Se...

Page 17: ...Figure 5 Compressor Electrical Connection Discharge Thermostat Connect the heater so that the connection point straddles the compressor seam weld Seam Weld Seam Weld ZR16 32K5 ZR38 54K5 WARNING Verify the correct crankcase heater voltage for the application and ensure heater is properly grounded Figure 6 Crankcase Heater 2013 Emerson Climate Technologies Inc 17 Printed in the U S A ...

Page 18: ... N AE4 1374 R1 Evapora ng Temperature C 29 24 19 14 9 4 1 6 11 160 150 66 61 140 56 130 51 120 46 110 41 100 36 90 31 80 26 70 21 20 10 0 10 20 30 40 50 60 Evapora ng Temperature F Figure 7 R 22 R 407C Scroll Operating Envelope 2013 Emerson Climate Technologies Inc 18 Printed in the U S A ...

Page 19: ...e as necessary to heat tube evenly Add braze material to the joint while moving torch around joint to flow braze material around circumference After braze material flows around joint move torch to heat Area 3 This will draw the braze material down into the joint The time spent heating Area 3 should be minimal As with any brazed joint overheating may be detrimental to the final result 2013 Emerson ...

Page 20: ...Application Engineering B U L L E T I N AE4 1374 R1 Figure 9 2013 Emerson Climate Technologies Inc 20 Printed in the U S A ...

Page 21: ...uration Shock loop Service Valve Angled valve fastened to unit Suction muffler Not required Alternate Configuration Component Description Tubing Configuration Shock loop Service Valve Straight through valve not fastened to unit Mass Suction muffler May be required Acts as dampening mass Table 3 Mounting Parts Model Frame Size Mounting Kit Grommet Sleeve ZR16 32K5 53 527 0044 15 027 0262 00 028 018...

Page 22: ... Shell Diameter e g 53 5 5 Inches 63 6 5 Inches Charge Allowance For System Table 5 Crankcase Heaters Model Frame Size Emerson Part No Volts Watts Leads EHP Product ZR16 32K5 53 240 40 21 018 0094 00 120 40 21 018 0094 01 240 40 21 018 0096 00 120 40 21 018 0096 01 ZR38 54K5 63 480 40 21 018 0096 02 575 40 21 018 0096 03 240 40 48 018 0096 04 480 40 48 018 0096 05 2013 Emerson Climate Technologies...

Reviews: