background image

9

© 2015 Emerson Climate Technologies, Inc. All rights reserved.

AE4-1395 R5

Compressor Selection & Change-Out

The replacement digital scroll compressor should be 

compared to the non-modulating compressor in at least 

these three areas:

1.  Performance – the full load capacity of the digital 

scroll should be approximately equal to the capacity 

of the compressor being replaced. In some cases 

in might make sense to 'right size' the compressor 

capacity for the load if the compressor is grossly 

oversized.

2.  Electrical – the digital scroll compressor RLA and 

LRA should be compared to the compressor being 

replaced. Contactor, wire, breaker/fuse, and run 

capacitor sizes should be evaluated.

3.  Mechanical – in most cases the compressor 

mounting will be identical for the non-modulating 

and the digital scroll. There could be minor 

differences in the suction and discharge tubing 

locations, as well as the height of the compressor. 

The following steps should be followed to remove the 

non-modulating compressor from the system. 

1.  Using an EPA approved refrigerant recovery 

machine, recover the system refrigerant charge 

from the low and high sides of the system.

2.  Disconnect and lockout the power supply.

 

Confirm that all voltage sources have been 

disconnected by using a voltmeter. Disconnect the 

conduits and wiring to the compressor and move 

them out of the way as much as possible.

3.  By using manifold gauges, verify that the system 

refrigerant charge is completely recovered from 

the system. Suction and discharge pressures must 

be 0 psig.

4.  Using a tubing cutter, cut the suction and discharge 

lines close to the compressor.

5.  Remove the compressor mounting bolts.
6.  Plug the compressor suction and discharge 

connections to prevent the spillage of oil from the 

compressor when removing it from the system.

7.  Using the appropriate lifting devices, carefully 

remove the compressor from the system.

The following steps should be followed to install the digital 

compressor into the system.

1.  Before removing the rubber plugs, install the 

compressor in the unit on the mounting grommets 

using the appropriate lifting devices.

2.  Install the compressor mounting bolts.
3.  Connect the suction and discharge lines using 

standard brazing practices.

4.  If the compressor has an external modulation valve 

and tubing (ZPD34-ZPD54K5, ZPD61-ZPD83KC, 

ZPD91KC, ZPD104KCE, ZPD122KCE, and 

ZRD36-81KC only) refer to 

Figure 6

 for the correct 

valve orientation and position. Wrap a wet rag 

around the valve and complete the assembly by 

brazing the valve and tubing into place.

5.  Check for leaks using nitrogen with a properly sized 

regulating and relief valve.

6.  Connect conduits and wiring to the compressor. 

Inspect and/or replace the contactor. If the 

compressor is 1-phase, install the correct run 

capacitor.

NOTICE

The above procedures for changing the 

compressor are not comprehensive and additional 

steps/procedures may be necessary.

Refrigerant Flow Control

In the system with a digital compressor, the refrigerant 

flow control valve is required to control flow across a wide 

range of flow rates and varying pressure differentials. 

Most balanced port thermostatic expansion valves can 

control flow down to about 40% of their rated capacity. 

Excessive hunting and loss of superheat control can 

result when asking a thermostatic expansion valve to 

operate outside of its design range. For this reason, 

the expansion device needs to be evaluated to ensure 

reliable operation over the expected operating range. 

Limiting the minimum compressor modulation rate to 

a value that the expansion valve can tolerate should 

be considered. Electronic expansion valves should be 

considered if modulation over the entire range of the 

compressor’s modulation range is anticipated.

Evaporator Air Flow

For the highest level of energy savings, comfort, and 

efficiency the variable capacity system should be capable 

of  varying  the  air  flow.  Variable  frequency  drives  and 

tapped  blowers  are  two  means  of  reducing  air  flow.  

Reducing  air  flow  in  humid  or  maritime  climates  is 

important to maintain coil temperatures low enough to 

Summary of Contents for Copeland Scroll Digital ZPD103KC

Page 1: ...ntrol 7 Application Tests Oil Level Verification 7 Excessive Liquid Floodback Tests 7 Operating Envelope Tests 7 Digital Compressor Retrofit Applications Reasons to Retrofit 7 Retrofit Applications To Avoid 8 Performance Modeling 8 System Modifications 8 Compressor Selection Change Out 8 Refrigerant Flow Control 9 Evaporator Air Flow 9 Condenser Air Flow 9 Modulation Control 9 Assembly Line Proced...

Page 2: ...s been placed on the user s safety Safey icons are explained below and safety instructions applicable to the products in this bulletin are grouped on Page 3 These instructions should be retained throughout the lifetime of the compessor You are strongly advised to follow these safety instructions Safety Icon Explanation DANGER indicates a hazardous situation which if not avoided will result in deat...

Page 3: ...y equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Personal safety equipment must be used Failure to follow these warnings could result in serious personal in...

Page 4: ...ulating its capacity from 10 to 100 A normally closed de energized solenoid valve is a key component for achieving modulation When the solenoid valve is in its normally closed position the compressor operates at full capacity or loaded state When the solenoid valve is energized the two scroll elements move apart axially or into the unloaded state During the unloaded state the compressor motor cont...

Page 5: ...ressor For vertical piping a trap every 20 feet should be sufficient to ensure proper oil return This recommendation is based upon a minimum 1500 fpm velocity or higher When the digital scroll compressor is part of a tandem a double riser should be considered to assure that the velocity remains above 1500 fpm when only the digital scroll is running Start Up and Shut Down To improve the starting ch...

Page 6: ...e Heaters A crankcase heater is required if the system charge exceeds the system charge limits listed in Table 2 For more information regarding regarding heater part numbers and installation location please refer to the equivalent non digital scroll Application Engineering bulletin listed on Page 4 Oil Type and Oil Removal Mineral oil is used in the ZRD KC compressors for R 22 applications Polyole...

Page 7: ...compressor without the need for an additional system controller For more information on the Emerson Commercial Comfort Controller please refer to AE8 1393 NOTICE For OEMs that choose their own controls package the controls must include the protection features incorporated into the Copeland Scroll Digital Compressor Controller Please consult with Application Engineering for a list of these requirem...

Page 8: ...nsitive components laboratories hospital operating and recovery rooms and equipment rooms that require constant cooling are all applications that would benefit from a modulating digital scroll Many of these are critical cooling applications and require equipment that is designed specifically for these applications Don t attempt to retrofit a non modulating HVAC unit in a critical application to on...

Page 9: ...the digital compressor into the system 1 Before removing the rubber plugs install the compressor in the unit on the mounting grommets using the appropriate lifting devices 2 Install the compressor mounting bolts 3 Connect the suction and discharge lines using standard brazing practices 4 If the compressor has an external modulation valve and tubing ZPD34 ZPD54K5 ZPD61 ZPD83KC ZPD91KC ZPD104KCE ZPD...

Page 10: ...prevent the build up of copper oxide The solenoid coil should be installed after the brazing operation so the leads are kept away from the brazing operation and the wet rag is able to fully contact the valve body Pressure Testing The pressure used on the OEM assembly line to meet the UL burst pressure requirement cannot be higher than 400 psig 27 6 bar for R 407C R 22 and 475 psig 32 8 bar for R 4...

Page 11: ...rant charge from the compressor system 3 Remove the cover from the small terminal box and remove the screw holding the coil to the valve using a Phillips screwdriver or appropriate size nut driver 4 Remove the coil from the valve and clean the area around the valve body to prevent debris and dirt from entering the system when changing the valve 5 Using manifold gauges double check to make sure the...

Page 12: ...ressures still do not move to normal values either the reversing valve if so equipped or the compressor is faulty Reconnect the compressor leads as originally configured and use normal diagnostic procedures to check operation of the reversing valve The solenoid coil should only be energized when it is installed on the solenoid valve Energizing the coil when it is not installed on the valve will re...

Page 13: ... 3s NOT PUMPING NOT PUMPING One Cycle of 15 seconds 15 seconds Figure 1 Digital Cycle Example Figure 2 Digital Scroll Cross Sectional View ZPD34 ZPD54K5 ZPD61 ZPD83KC ZPD91KC ZPD104KCE ZPD122KCE and ZRD36 81KC Note Modulation tubing is show for reference only Refer to Figure 6 for the correct modulation tubing configuration ...

Page 14: ...ogies Inc All rights reserved AE4 1395 R5 Figure 3 Digital Scroll Cross Sectional View ZPD103KC ZPD120KC ZPD137 182KC and ZRD94 125KC Removable External Solenoid and Coil Floating Seal Cavity Seal Cavity Vent 90 Frame Digital Scroll ...

Page 15: ...E4 1395 R5 Figure 5 Discharge Thermistors Figure 4 Compressor Capacity Graph ppt 3 23 2010 3 14 PM 1 0 10 20 30 40 50 60 70 80 90 100 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Compressor Capacity Percent of Full Load 15 Second Operating Cycle Solenoid On Time Seconds ...

Page 16: ...ZPD54K5 ZPD61 ZPD83KC ZPD91KC ZPD104KCE ZPD122KCE and ZRD36 81KC Figure 7 Tandem ZPD34 ZPD54K5 ZPD61 ZPD83KC ZPD91KC ZPD104KCE ZPD122KCE and ZRD36 81KC Arrow on valve Must point to suction Oil Equalization Line Suction Gas Equalization Manifold Discharge Manifold Assembly Suction Manifold Assembly Solenoid Valve ...

Page 17: ...sn t running Allow time to cool Put the system back into operation and retest Start Measure the voltage at the modulation coil terminals Is voltage present coinciding with the modulation cycle Troubleshoot the modulation control WARNING Disconnect and lockout the power before proceeding Remove one wire from the modulation coil Coil has continuity and isn t grounded Replace modulation coil Replace ...

Page 18: ...8KC 8 3 6 Table 1 Copeland Scroll Digital Family Features Model Digital Modulation Valve Discharge Gas Temperature Protection Discharge Check Valve Internal Pressure Relief IPR Valve Modulation Control ZPD34 54K5 Required Accessory External Sensor Required No Yes 15 Second Cycle ZRD36 48KC ZPD61 ZPD83 ZRD61 81KC Internal Top Cap Thermistor ZPD103 ZPD120 ZPD137 182KC Installed On Compressor Externa...

Page 19: ...Coil Tubing Kit 998 0090 02 ZPD34 54K5 ZPD61 ZPD83 ZPD91KC ZRD34 81KC Tubing kit is for 7 8 compressor suction All coils have 1 4 spade electrical terminals Modulation Valve Tubing Kit 998 0090 01 Modulation Valve 910 0182 00 ZPD103 ZPD120 ZPD137 182KC ZRD94 125KC All coils have 1 4 spade electrical terminals 24V Coil Holding VA Max 60 HZ 20 0 998 0060 03 120V Coil Holding VA Max 60 HZ 17 3 998 00...

Reviews: