Ex. If Value = 50, then it's
150rpm/sec
These values need to be re-configured
only if different shutdown, ramp up &
ramp down rates are required.
211
Speed Ramp-up
Rate Config
Option
2 Bytes
16.0
0 = Not Configured
Can be configured in
increments of "20" (20 to 120).
Decimal value of 20 =
60rpm/sec
Ex. If Value = 20, then it's
60rpm/sec
20
212
Speed Ramp-
down Rate Config
Option
2 Bytes 16.0
0 = Not Configured
Can be configured in
increments of "20" (20 to 120).
Decimal value of 20 =
60rpm/sec
Ex. If Value = 20, then it's
60rpm/sec
20
213
Ramp-up Speed
Level Config
Option during
Start-up
2 Bytes 16.0
100RPM/bit
0 = Default Ramp-up profile at
start-up
Ex. 15 = 1500RPM
Range: 1500RPM to
3500RPM in 100RPM
increments
0
Range: 1500RPM to 3500RPM in
100RPM increments. Drive cannot be
configured outside this band.
*Note: After 10 occurrences of a particular lockout related fault within 10hours time period, the drive will go into hard
lockout and need to be power cycled to clear the fault.