30
C6.1.6/0117-1017/E
3
Installation
WARNING
High pressure!
Injury to skin and eyes possible!
Be careful when opening
connections on a pressurized item.
Copeland EazyCool ZX condensing units are delivered with a holding charge of neutral gas.
The condensing unit should be located in such a place to prevent any dirt, dust, plastic bag, leaves
or papers from covering the condenser and its fins.
The unit must be installed without restricting the airflow.
A clogged condenser will increase the condensing temperature, thus reduce the cooling capacity,
and lead to a high-pressure switch tripping. Clean the condenser fins on a regular basis.
3.1 Condensing unit handling
3.1.1 Transport and storage
WARNING
Risk of collapse! Personal injuries!
Move condensing unit only with
appropriate mechanical or handling equipment according to weight. Keep in
the upright position. Stack pallets on top of each other when not exceeding
300 kg. Do not stack single boxes on top of each other. Keep the packaging
dry at all times.
Figure 19: Transport and storage
3.1.2 Weights
Condensing units
Standard compressors
Digital compressors
Medium
temperature
Weight
(kg)
Low
temperature
Weight
(kg)
Medium
temperature
Weight
(kg)
ZXME020E
76
ZXLE020E
79
ZXME025E
79
ZXLE025E
81
ZXME030E
79
ZXLE030E
81
ZXDE030E
82
ZXME040E
91
ZXLE040E
93
ZXDE040E
104
ZXME050E
108
ZXLE050E
106
ZXDE050E
108
ZXME060E
112
ZXLE060E
116
ZXDE060E
112
ZXME075E
118
ZXLE075E
126
ZXDE075E
118
Table 26: Weights