13
© 2016 Emerson Climate Technologies, Inc.
AE8-1384 R5
Parameters can be write using Function code 16 (Preset Multiple Registers)
Location
in Hex Parameter
Message
Length in
Bytes
Message
Length
With Zero
Stuffing
100
Customer Id Code
4
8
104
Customer Location
17
34
115
Customer Name
17
34
126
Compressor Model Number Modified
18
36
138
Compressor serial number
12
24
144
Application code
3
6
147
Temperature code
4
8
14B
Refrigerant code
7
14
152
Functional Configuration
2
2
154
Compressor run time to count as short
cycle
1
2
Range: 1 min to 6 min
155
Scroll High Temp Trip
2
2
Range: 110 deg C to 150 deg C
157
Scroll High Temp Reset
2
2
Note: Reset set point value should
be always (Trip set point value -
30 deg C)
159
No. of Events to Phase Loss Lockout
1
2
Range: 4 to 24
15A
Future Use
15B
Future Use
15D
Future Use
15F
No.of Events to Scroll High Temp
Lockout
1
2
Range: 4 to 36
160
No.of Events to Short Cycling Warning
1
2
Range: 20 to 200
16A
Write Command
2
2
Options: 0x0800(Alarm Reset) &
0x8000(Module Reset)
Table 4 – CoreSense Modbus Map Continued