ControlWave Instruction Manual (CI-ControlWave)
Revised Nov-2010
Service & Troubleshooting
5-15
Module /
Board
LED Name
LED Color
Function and Location
point)
LED OFF= no UDI input activity. See
.
RTD
RTD Board Status
Red/Green
ON RED = Fail state/board not recognized.
ON GREEN = Normal state. See
RTD
Range (8 LEDs – 1 per point)
Red
LED ON = RTD over-range or RTD under-
range condition. See
.
RTD
Range (8 LEDs – 1 per point)
Green
LED ON = RTD in range. See
LLAI
LLAI Board Status
Red/Green
ON RED = Fail state/board not recognized.
ON GREEN = Normal state. See
LLAI
Range (12 LEDs – 1 per point)
Red
LED ON = LLAI over-range or LLAI under-
range condition. See
.
LLAI
Range (12 LEDs – 1 per point)
Green
LED ON = LLAI in range. See
1
3
I
O
(Red)
(Red)
(Green)
MC LED
PWRFAIL LED
PWRGOOD LED
TB1
Watchdog
Connector
TB2
Input Power
Connector
POWER SWITCH
Captured Panel Fastener
Captured Panel Fastener
1
5
1
5
+VIN (+22.2Vdc to +30Vdc for +24V supply)
(+VINF) Connected to TB2-1 (or se20.0Vdc to +30Vdc supply)
(-VIN) (1st Supply Ground)
(-VINF) (2nd Supply Ground) Internally connected to TB2-3
Chassis Ground (CHASSIS)
I Pressed = Power ON
O Pressed = Power OFF
Reg3.3Vdc, +5vdc, +12Vdc (Optional), & -12Vdc (Optional)
Supplies are above minimum acceptable limits.
=
= Bulk or Regulated Power Out Of Spec.
Master Clear is active asserted 2msc after
PWR_FAIL has been asserted.
=
1
3
TB1 Redundancy Connections:
VO - WD MOSFET Switch Output
VI - Relay Power (+24Vdc)
VR - Redundant Unit Control Input
TB1 MOSFET Connections:
VO - WD MOSFET Switch Output
VI - WD MOSFET Switch Input
Not Used
Figure 5-10. Power Supply/Sequencer Module’s TB1, TB2 & LED Designations