DO NOT CONNECT GROUND
TO TRANSFORMER SECONDARY
Solution #2 – Isolation Transformer
Transformer KVA = 1.5 x Rated Armature Current x 120 Vac (or 240)
Example
: Your DC Motor has a 10 A armature
KVA = 1.5 x 10 A x 120 Vac = 2.4 KVA (use 2.5 KVA)
L1
L2
12
TB2
Focus 3 Non-regen
DC Drive
120 / 240
VAC Input
120 / 240
VAC Output
Isolation Transformer
Heat Sink
GND Lug