n=0
:
At zero speed
At.SP
: At speed
Lo.SP
: At minimum speed
hEAL
: Drive ok
Act
:
Drive active
ALAr
: General drive alarm
I.Lt
:
Current limit active
At.Ld
: At 100% load
USEr
: User programmable
Fr
:
Voltage proportional to motor speed
Ld
:
Voltage proportional to motor load
A
:
Voltage proportional to output current
Por
:
Voltage proportional to output power
USEr
: User programmable
See the
Commander SK Advanced User Guide
.
3
:
3kHz
6
:
6kHz
12
:
12kHz
18
: 18kHz
See the
Commander SK Technical Data Guide
for drive derating data.
0
: No autotune
1
: Non-rotating static autotune
2
: Rotating autotune
No
Function
Range
Defaults
Type
35
Digital output control (terminal B3)
n=0, At.SP, Lo.SP, hEAL,
Act, ALAr, I.Lt, At.Ld, USEr
n=0
RW
This parameter is automatically changed by the setting of Pr
12.
When Pr
12
automatically controls the setting of this parameter, this parameter cannot be changed.
NOTE
A change to Pr
35
is set by pressing the
MODE key on exit from parameter edit mode.
See the
Commander SK Advanced User Guide
.
NOTE
M
Terminal B3 can also be configured as a digital input, frequency output or PWM output.
Refer to the
Commander SK Advanced User Guide
. for more information.
NOTE
No
Function
Range
Defaults
Type
36
Analog output control (terminal B1)
Fr, Ld, A, Por, USEr
Fr
RW
A change to Pr
36
is set by pressing the
MODE key on exit from parameter edit mode.
NOTE
M
No
Function
Range
Defaults
Type
37
Maximum switching frequency
3, 6, 12, 18 kHz
3
RW
18kHz is not available on Commander SK size B, C and D 400V units and size D 200V units.
NOTE
With drive firmware V01.07.01 onwards, the 400V size C drive will have an actual switching
frequency of 3kHz when the output frequency is below 6Hz.
NOTE
No
Function
Range
Defaults
Type
38
Autotune
0 to 2
0
RW