CASH VALVE™

 TYPE B ¼" TO 2" FOR CRYOGENIC SERVICE

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Before installation, these instructions must be carefully read and understood.

DESCRIPTION

The Type B regulator is a fully automatic 
pressure regulating valve designed for 
cryogenic service in the pressure build-up 
circuit. Because the Type B may be used for 
either cryogenic liquids or gases, it may be 
installed either before or after the pressure 
build-up coil.

SPECIFICATION DATA

Service:

 Cryogenic liquids and gases (pressure 

reducing or build-up service)

Sizes:

 ¼", ⅜", 

1

/

2

", 

3

/

4

", 1", 1 ¼", 1 ½" and 2"

Connections:

 Threaded internal inlet and outlet

Body Material:

 Bronze

Temperature Rating:

 +150°F (339°K) to  

-320°F (78°K)

Maximum Initial Pressure:

 

400 psi (27.6 bar)

CONSTRUCTION

Bronze body, internal trim, and diaphragms; 
Teflon seat, diaphragm gasket, and bottom 
plug gasket; stainless steel pressure spring.
All parts are commercially cleaned for 
oxygen service.

GENERAL INSTALLATION INSTRUCTIONS

Install a Y-Type or equivalent strainer upstream 
of the Type B. The built-in strainer screen is 
secondary protection only.

The Type B regulator should be installed in the 
horizontal position with the spring chamber up 
or down. For other installation requirements 
consult the factory. For ease of operation and 
maintenance, it is suggested that manual 
shutoff valves be installed upstream and 
downstream from the valve. Before installing 
the valve, the piping and the valve should be 
thoroughly flushed out to remove any foreign 
material. Install the valve with the inlet pipe 
fitted to the inlet connection identified on the 
valve body. Use a good pipe joint compound on 
the male pipe threads and do not over tighten 
the valve connections.

Emerson.com

© 2018 Emerson. All rights reserved.

VCIOM-10796-EN 22/01

WARNING

Failure to follow these instructions or to properly 
install and maintain this equipment could result in 
an explosion, fire and/or chemical contamination 
causing property damage and personal injury 
or death.

Cash Valve regulators must be installed, operated 
and maintained in accordance with federal, 
state and local codes, rules and regulations 
and Emerson Process Management Regulator 
Technologies, Inc. instructions.

If the regulator vents gas or a leak develops in 
the system, service to the unit may be required. 
Failure to correct trouble could result in a
hazardous condition.

Installation, operation and maintenance 
procedures performed by unqualified personnel 
may result in improper adjustment and unsafe 
operation. Either condition may result in 
equipment damage or personal injury. Only 
a qualified person shall install or service the 
B Series regulator

CALIFORNIA PROPOSITION 65 WARNING

This product can expose you to chemicals 
including lead, which is known to the State of 
California to cause cancer, birth defects or other 
reproductive harm. For more information, go to 
www.P65Warnings.ca.gov.

INTRODUCTION

Scope of the Manual

This manual provides instructions for the 
installation, adjustment, and maintenance for 
the B Series pressure regulators. 