8
Bettis Q-Series
Installation Guide
February 2017 DOC.IG.BQC44.1 Rev. 1
4.3 Connecting 2-Wire proximity switches
IMPORTANT
The below mentioned typical switch specifications
are applicable for non-hazardous areas.
1. Before connecting the switches, check the
model code on the Control Module label.
QCXX.xxxNxx = 2-Wire NAMUR proximity
2 Guide the cable(s) through the electrical
entry(ies).
- Use and mount cable glands as required by
national or local legislation.
3. Make connections as shown in figure 4.9 and
table 4.5.
4. Mount the Control Module cover. Take care that
the cover seal is in place to comply to dust and
water tightness according to IP66 or NEMA4X.
-3°
15°
75°
93°
0°
90°
3mA
1mA
-3°
15°
75°
93°
0°
90°
3mA
1mA
≥
3mA
≤
1 mA
≥
3mA
≤
1 mA
-3°
15°
75°
93°
0°
90°
3mA
1mA
-3°
15°
75°
93°
0°
90°
3mA
1mA
≥
3mA
≤
1 mA
≥
3mA
≤
1 mA
Switch
operation
Open Switch
Unswitched
Switched
Rotation
Close Switch
Unswitched
Switched
Rotation
Fig 4.8
Switch characteristics 2-wire NAMUR
proximity switch
Fig 4.7
Switch characteristics 2-wire 230VAC
proximity switch
Switch signal and adjustable switch range
2-wire NAMUR proximity switch
-3°
15°
75°
93°
0°
90°
Switch
Switch signal and adjustable
switch range
Close
switch
Open
Switch
Rotation
Switched
Unswitched
Switch
operation
2-Wire 115V
proximity
switch
Si
gn
al
IMPORTANT
For hazardous area installations see instructions in
paragraph Chapter 11.
Table 4.5 2-Wire NAMUR proximity switches
Option code
N
Type
2-wire inductive, normally closed
Voltage
8 VDC nominal
Output
Unswitched: > 3mA
Switched:
< 1mA
Temperature
See table 4.1
Compliant to
DIN EN 60947-5-6 (NAMUR)