Maintenance, fault finding, and repair
[85]
CAUTION!
7.
Adjust the voltage steps -12 V, -14 V, -16V, and -18 V as shown in
with
the calibration gauge, and check the distance with the micrometer screw of the
gauge. Continue the check with the voltage steps -8 V, -6 V, -4 V, and -2 V, and
check the distance.
Figure 10-1: Linearity check
x: Measuring range beginning and end value (-x to 0 to x)
Example: x = 1 mm if an EZ 1080 sensor with a standard measuring range of -1 mm to +1 mm is
used.
The deviation between the ideal distance, described by the
, and the
measured distance must be lower than 1
%
.
10.6
Firmware update
Any work on the system may impair machine protection.
The firmware of the EZ 1000 can be updated by using Machine Studio.
Note
WayCon recommends saving the configuration of the EZ 1000 converter before starting the update
process. See operating manual Machine Studio - General Functions (MHM-97879) for details.