Instruction Booklet
IB020003EN
Effective January 2021
AMPGARD RVSS
Reduced Voltage Soft-Starter
User Manual
Figure 83. Modbus Serial - Modal Configuration popup.
Open the Windows Device Manager, and double-click the Ports (COM &LPT) branch to determine the COM port assignment for the USB
). The port number will be chosen from the drop-down list in the inControl Modal Configuration screen,
.
Also, double-click the COM port entry to open the port properties window. Set the baud rate as high as possible, but either
9600
,
19200
, or
38400
. Set parity to
Even
. Be sure that Stop Bits is
1
. Click
OK
to save changes.
ote:
N
You must have administrator rights to make changes to the port settings. If you do not, the window will appear to accept your entries, but will not. This
will result in
inControl
not making a workable connection (see
Also, the heading on the Windows Port Properties window will reflect the connection medium. In this example case, a cable with a dongle was used, so the
connection shown is a UART Bridge, assigned to COM5.
Figure 84.
Choose higher
Even
Windows COM port properties.