J12 and J13 Inputs and Outputs
shows the input and output signals connected to I/O Board
connectors J12 and J13. The table lists the input names shown on
the schematic diagrams, the I/O Board connector wire numbers,
connector pinouts, the signal names where appropriate, and their
functions. This table is a portion of
Table 8. I/O Board connectors J12 and J13 signals
Input name
Wire
numbers
Connections
Signal
name
Function
IP0
60, 61
J12-1, J12-2
DIN0
External Fault
IP1
62, 63
J12-3, J12-4
DIN1
Starter main contactor status Input
IP2
64, 65
J12-4, J12-6
DIN2
Bypass contactor status input
IP3
66, 67
J12-7, J12-8
DIN3
Field-wire Reset
IP4
68, 69
J12-9, J12-9
DIN4
SS2 Bypass mode selector switch input
IP5
70, 71
J12-11, J12-12
DIN5
Profile mode selector input
IP7
74, 75
J12-15, J12-16
DIN7
Start relay (CR) input
Output name
Wire
numbers
Connections
Function
K3
K3, 24N (T3)
J13-6, J13-13
RY1 Bypass contactor control relay BX control
K2
K2, 24N (T2)
J13-7, J13-15
RY2 Main contactor control relay MX control
K4
K4, 24N (T4)
J13-3, J13-11
TRPX relay control
K1
K1, 24N (T1)
J13-8, J13-16
Ready
K5
K5, 24N (T5)
J13-2, J13-10
Up-to-speed detection
K6
K6, 24N (T6)
J13-1, J13-9
I% FLA > 90% of Current Limit %
shows more information about the I/O Board status LEDs
shown in
Table 9. I/O board status LED functions
LED
Function
D36
Indicates when K6 SSR is energized and any on of the phase current RMS
values is above 90% of the Current Limit % setting.
D35
Indicates when K5 SSR is energized and the RVSS is at the Bypass
transition point in speed (UTSD) and current (the current has reduced back
down to Transition Threshold % of FLA).
D34
Indicates when K4 SSR is energized. K4 drives relay TRPX, the RVSS fault
relay. TRPX is energized when there is a system fault.
D32
Indicates when K2 SSR is energized. K2 drives relay RY2, which energizes
the Bypass Contactor pilot relay, BX, in normal operation.
D31
Indicates when K1 SSR is energized and the I/O Board is in
operational condition with no internal faults and the RV Soft-Start
is Ready.
D33
Indicates when K3 SSR is energized. K3 drives relay RY1, which energizes
the Main Contactor pilot relay, MX, in normal operation.