Operating instruction 

Pressure actuated Fan Speed Control  

FSX / FSY / FSM 

 

 

 

Emerson Climate Technologies GmbH  

www.climate.emerson.com/en-gb

 

Am Borsigturm 31 I 13507 Berlin I Germany 

Date: 04.09.2019 

FSY-FSX-FSM_OI_ML_R14_0716010.docx 

G e n e r a l   i nf o r ma t i o n : 

FS regulates the speed of fan motors according to 

pressure changes. Make sure that the motor is approved 

by the motor/unit manufacturer for variable speed by 

means of phase cutting (TRIAC).

 

  S a f e ty   i n s tr u c t i o n s : 

 

Read operating instructions thoroughly. Failure 

to comply can result in device failure, system 

damage or personal injury. 

 

According to EN 13313 it is intended for use by 

persons having the appropriate knowledge and 

skill. 

 

Before opening any system make sure pressure in 

system is brought to and remains at atmospheric 

pressure. 

 

Do not exceed the specified maximum ratings for 

pressure, temperature, voltage and current. 

 

Before installation or service disconnect all 

voltages from system and device. 

 

Observe and avoid mechanical damage of 

component housing. 

 

Do not use any other fluid media without prior 

approval of EMERSON. Use of fluids not listed 

could result in change of hazard category of 

product and consequently change of conformity 

assessment requirement for product in 

accordance with European pressure equipment 

directive 14/68/EU. 

 

Ensure that design, installation and operation are 

according 

to European and national 

standards/regulations. 

 

Disposal:  Electrical and electronic waste must 

NOT be disposed of with other commercial waste. 

Instead, it is the user responsibility to pass it to a 

designated collection point for the safe recycling 

of Waste Electrical and Electronic Equipment 

(WEEE directive  2012/19/EU). For further 

information, contact your local environmental 

recycling center. 

 
S e t t i n g :    

If desired set point differs from factory setting, follow 

the procedure for setting 

before any installation

Factory set point: 

Type 

Refrigerant  Temp. 

(°C) 

Pressure 

P-band 

fix

 

FS_-41_ 

R134a 

36 

8 bar  2.5 bar 

R1234ze 

46 

R513A 

34 

R450A 

41 

FS_-42_ 

R404A 

35 

15 bar  3.8 bar 

R507 

35 

R452A 

37 

R407F 

38 

R448A 

39 

R449A 

39 

R407F 

39 

R407C 

42 

R22 

42 

FS_-43_  R410A 

38 

21.8 bar  4.6 bar 

 

Fig. 1 

 Bottom view  

 Allen Key 

 Setting Screw 

 Clockwise 

 Sealing plug 

 Counterclockwise 

1.

 

Remove sealing plug and insert 2 mm or 5/64" 

Allen key into setting screw. Turn Allen key 

clockwise (+) or counterclockwise (-) to readjust the 

setting. Do not turn setting screw 

more than 3 

turns clockwise

 (+3).  

Use following table as a quick guideline for setting:

 

Pressure changes per turn of adjusting screw:

 

Type 

FS   -41_   FS   -42_

 

FS   -43_

 

Pressure 

range (bar) 

4.0...12.5   9.2…21.2   12.4…28.4  

Turn 

clockwise 

+1.2 bar  +2.5 bar 

+3.3 bar 

Turn 

counter-

clockwise 

-1.2 bar 

-2.5 bar 

-3.3 bar 

2.

 

After adjustment insert sealing plug and make sure 

that it is properly fitted.  

Notes:  

 

IP65 protection requires firmly sealed plug. 

 

Tolerances for condensing temperatures set point: 

±

2K. 

Readjustment to factory set point: 

Turn setting screw counterclockwise until end-stop. 

Then turn setting screw clockwise: 

5 turns for FS   -41  ,  

3 turns for FS   -42   or  

5-1/2 turns for FS   -43  . 

  Partial voltage is applied even if motor is not 

running. Disconnect voltage for service on motor or 

FS! 
M o u n t i n g   l o c a t i o n :  

see Fig. 2 and Fig. 3

 

I n s t a l l a t i o n : 

Direct mounting via pressure connection or indirect 

mounting on housing bracket with capillary tube or 

sweat pressure connection. 

Threaded connection: (see Fig. 4) 

 

For tightness the use of copper gasket (

 Fig. 4) on 

7/16”-20UNF female connection is required. 

Brazing:

 

(see Fig. 5) 

 

Perform  and consider the brazing joint as per 

EN 14324. 

 

Before and after brazing clean tubing and brazing 

joints. 

 

Minimize vibrations in the piping lines by 

appropriate solutions. 

 

Do not exceed the max. body temperature of 

70°C! 

E l e c t r i c a l   c o n ne c t i o n   f o r   F S F - N _ _ : 

Notes: 

 

Entire electrical connections have to comply with 

local regulations.  

 

Use proper cable diameter for wiring of motor.

  

 

Do not use with two-speed motors. 

 

Push plug slightly on the pins of controller.  

 

Direction of plug in 90° steps possible (Fig. 6) 

 

No gasket required. 

 

Fasten screw with 0,3 Nm.  

 

Plug cannot be repaired. In case of failure replace 

connector. 

P r e s s ur e   T e s t : 

After completion of installation, a pressure test must be 

carried out as follows: 

‒ 

according to EN 378 for systems which must comply 

with European pressure equipment directive 

14/68/EU. 

‒ 

to maximum working pressure of system for other 

applications. 

 

Warning

:  

 

Failure to do so could result in loss of refrigerant 

and personal injury. 

 

The pressure test must be conducted by skilled 

persons with due respect regarding the danger 

related to pressure. 

L e a ka g e   T e s t :  

Conduct a  tightness test according to EN 378-2 with 

appropriate equipment and method to identify leakages 

of external joints.  

W i r i n g :   ( s e e   F i g .   7 ) 

Note: 

Use fuse type/size recommended by motor 

manufacturer and break switch. Consult motor 

manufacturer for capacitor size (Cb). 

O p e r a t i o n :   

Note: Before operation the customer has to qualify 

the functionality and reliability of FS

   

_+ FSF-

N

     in 

combination with the fan motors!

 

 

T e c h ni c a l   D a ta :    

Supply voltage 

15%, -20%  

(50-60 Hz) 

Nominal Current  

FSY  

FSX/FSM 

 

0.1 – 4.0A  

0.5 – 4.0A 

3.0A at 55°C - Fig. 8 

Fig. 8

 

 

Max.operating Pressure PS 

FS    -41  :  

FS    -42  :  

FS    -43  : 

27 bar 

32 bar 

43 bar 

Max. Test Pressure PT 

FS    -41  :  

FS    -42  :  

FS    -43  : 

30 bar 

36 bar 

48 bar 

Temperatures 

medium at pressure connection  

operating (ambient) 

 

Max. 70°C 

-20…+55°C 

Medium 

Compatibility 

R410A 

R134a 

R404a, 

R507 

R407C 

R407A 

R407F 

R1234ze  R452A 

R448a 

R449a 

R450A 

R513A 

R22 

Protection class  

IP 65 (EN 60529/IEC 529)  

Markings  

(FS     + FSF-N     ) 

 (EMC 2014/30/EU,  

LVD 2014/35/EU,  

RoHS 2011/65/EU) 

 

 

 

Summary of Contents for Alco Controls FSX Series

Page 1: ...ar 3 3 bar 2 After adjustment insert sealing plug and make sure that it is properly fitted Notes IP65 protection requires firmly sealed plug Tolerances for condensing temperatures set point 2K Readjustment to factory set point Turn setting screw counterclockwise until end stop Then turn setting screw clockwise 5 turns for FS 41 3 turns for FS 42 or 5 1 2 turns for FS 43 Partial voltage is applied ...

Page 2: ...schließen Hinweis Voraussetzung für IP65 Die Toleranzen für den Einstellpunkt der Verflüssigungstemperatur sind 2K Zurücksetzen auf Werkeinstellung Sie erhalten wieder die Werkseinstellung wenn Sie die Einstellschraube zuerst gegen den Uhrzeigersinn bis zum Anschlag drehen und dann 5 Umdrehungen bei FS 41 3 Umdrehungen bei FS 42 oder 5 1 2 Umdrehungen bei FS 43 im Uhrzeigersinn Der Motor steht imm...

Page 3: ...es La protection IP 65 requiert une bonne tenue du capuchon d étanchéité Tolérances pour températures de condensation 2K Pour retrouver le point de réglage d usine Tourner la vis de réglage dans le sens inverse des aiguilles d une montre jusqu à l arrêt Tournez ensuite la vis de réglage dans le sens horaire FS 41 5 tours FS 42 3tours ou FS 43 5 1 2 tours Une tension partielle est présente même si ...

Page 4: ...asegúrese de que queda apretado adecuadamente Notas La protección IP65 requiere un cierre correcto Tolerancia para temperatura de condensación en 2K Reajuste al punto de ajuste de fábrica Para reajustar el control FS a la presión inicial de fábrica girar el tornillo de ajuste en el sentido contrario de las agujas del reloj hasta el tope final después girar en sentido horario 5 vueltas para FS 41 3...

Page 5: ...otezione e assicurarsi che sia correttamente inserito Nota Per la protezione IP65 si richiede il corretto bloccaggio a tenuta del tappo di protezione Tolleranza sulle temperature di condensazione 2K Regolazione di nuovo al setpoint di fabbrica ruotare la vite di regolazione in senso antiorario fino al suo bloccaggio Quindi ruotare la vite di regolazione in senso orario rispettivamente di 5 giri FS...

Page 6: ...ратуре конденсации составляет 2К Возврат к заводским настройкам Поверните установочный винт против часовой стрелки до упора Затем поверните установочный винт по часовой стрелке на 5 оборотов для FS 41 на e оборотов для FS 42 на 5 1 2 оборотов для F 43 Электродвигатель находится всегда под частичным напряжением даже если он не вращается Прежде чем приступить к ремонтным или сервисным работам на эле...

Page 7: ...itore di liquido Ресивер Fan motor with variable speed Lüfter mit variabler Drehzahl Variateur de vitesse variable Moto ventilador con variación de velocidad Elletroventilatore a velocita variabile Электродвигатель вентилятора с переменной скоростью Evaporator Verdampfer Evaporateur Evaporador Evaporatore Испаритель Fig Рис 4 Fig Рис 5 Fig Рис 6 Fig Рис 7 Blue blau bleu azul blue Синий Brown braun...

Reviews: