Table 4 - CoreSense Modbus Map
NOTE::
Num
ber of registers value to be send in the query = Number in the column “Message Length With Zero Stuffing” / 2 (e.g. number
of reg required to read “Seven day Warning history with cumulative count” is 36 (72/2)
Read Only Data
Read Write Data
Write Only Data
Parameters can be read using Function code 4 (Read Input Register)
Location
in Hex
Parameter
Message
Length in
Bytes
Message
Length
With Zero
Stuffing
Description
300
CoreSense Module Firmware Version
8
16
308
CoreSense Module Model Number
12
24
314
ASSET Serial Number
12
24
320
ASSET Model Number
18
36
332
CoreSense Module Serial Number
11
22
33D
Division Name
29
58
35A
Product Code
9
18
363
Product Name
7
14
36A
Product type
1
2
36B
Endian Convention
1
2
36C
Dip switch Setting
2
2
Unused (18 bytes)
380
Alarm Code
1
2
0 - Normal Operation
1 - Loss of Communication to E2
2 - Open OR Short Spare Thermister Warning
3 - Open OR Short Scroll Thermister Warning
4 - Short Cycle Warning
5 - Module Low Voltage Trip
6 - Spare High Temperature Trip
7 - Missing Phase Trip
8 - Scroll High Temperature Trip
9 - Motor Thermister Open OR Short Trip
10 - Motor High Temperature Trip
11 -Short Cycle Lockout
12 - Spare High Temperature Lockout
13 - Motor High Temperature Open OR Short Lockout
14 - Reverse Phase Lockout
15 - Missing Phase Lockout
16 - Scroll High Temperature Lockout
17 - Motor High Temperature Trip Lockout
18 - P47 Module Failure