background image

CASH VALVE

 A36 PRESSURE REDUCING OR PRESSURE BUILD-UP REGULATOR

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Before installation, these instructions must be carefully read and understood.

DESCRIPTION

The Type A-36 regulator is a fully automatic 
pressure regulating valve designed for 
cryogenic service in the pressure build-up 
circuit. Because it may be used for either 
cryogenic liquids or gases, it may be installed 
either before or after the pressure build-up 
coil.

SPECIFICATION DATA

Service: 

Cryogenic liquids and gases 
(pressure reducing or 
pressure build-up service)

Sizes: ⅜"
Connections: 

Threaded internal inlet and 
outlet

Body material:  Bronze or Stainless Steel
Temperature
rating: 

+150°F (65°C) to 
-320°F (-195°C)

Maximum
initial pressure:  600 psig (41.4 bar)

Emerson.com/FinalControl

© 2020 Emerson. All rights reserved.

VCIOM-15035-EN 20/08

INSTALLATION INSTRUCTIONS

The Type A-36 regulator can be installed in 
any position. For ease of maintenance and 
reference however, it is suggested that the 
valve be installed in a horizontal line with 
the spring chamber upright. For convenient 
operation and maintenance, manual shut-
off valves should be installed upstream and 
downstream from the valve. Before installing 
the valve, the piping should be throughly 
flushed out to remove any foreign material. 
Install the valve with the inlet pipe in proper 
relationship to the flow arrow stamped on the 
valve body.

OPERATION INSTRUCTIONS

Adjusting the Delivery Pressure

The regulator's delivery pressure setting is 
adjusted by turning the adjusting screw (1) at 
the top of the spring chamber after loosening 
the adjusting screw lock nut (2). To increase 
the delivery pressure, turn the adjusting 
screw clockwise (into the spring chamber). 
To decrease the delivery pressure, turn the 
adjusting screw counter-clockwise (out of the 
spring chamber). Tighten the adjusting screw 
lock nut after the adjustment has been made.

NOTE

When adjusting the delivery pressure, draw flow and 
shutoff downstream to check pressure set.

MAINTENANCE INSTRUCTIONS

CAUTION

Before attempting to replace any spare parts, 
be sure to shut off all pressure connections to 
the valve. With the valve closed however, system 
pressure could still be locked between the 
shut-off valve and the inlet and/or outlet sides of 
the regulator. Before proceeding with any valve 
service, be certain to relieve the pressure from 
both sides of the regulator.

1.  Loosen Lock Nut ¼ turn and loosen 

Adjusting Screw until the Pressure Spring 
is no longer under tension. See Figure 1.

 

Note: 

When installing the Adjusting Screw 

during re-assembly, tighten the screw 
until the Lock Nut just touches the Spring 
Chamber. When the Valve is placed in 
service the pressure setting should be 
very close to the original setting.

2.  Loosen and remove Spring Chamber (with 

pressure spring) and bottom plug (with 
piston spring). With screwdriver placed 
in piston bottom slot, loosen and remove 
lock nut on top of diaphragm. Disassemble 
diaphragm and remove pusher post from 
piston. Remove piston and pusher post 
from valve.

3.  Replace Diaphragm, piston, seat disc, 

pusher post, and gaskets with components 
included in Kit. Diaphragm and pusher post 
gaskets must be given a very light coating 
of Flourolube LG-120 or oxygen compatible 
lubricant and installed between Body and 
Diaphragm Assembly.

4.  Retighten Spring Chamber to 50-60 ft/lbs. 

torque.

5.  Retighten Bottom Plug to approximately 

125 in./lbs. torque.

 

Important: 

DO NOT OVERTIGHTEN.

6.  Reset Adjusting Screw and tighten Lock 

Nut - see NOTE in step 1.

Reviews: