Reference Manual
00809-0100-4793, Rev CA
August 2004
3-5
Rosemount 8742C
Figure 3-4. Incline or Decline
Orientation
Horizontal installation should be restricted to low piping sections that are
normally full. Orient the electrode plane to within 45 degrees of horizontal in
horizontal installations. A deviation of more than 45 degrees of horizontal
would place an electrode at or near the top of the flowtube thereby making it
more susceptible to insulation by air or entrapped gas at the top of the
flowtube.
Figure 3-5. Horizontal Flowtube
Orientation
The electrodes in the Rosemount 8711 are properly oriented when the top
of the flowtube is either vertical or horizontal, as shown in Figure 3-6. Avoid
any mounting orientation that positions the top of the flowtube
at 45° from the vertical or horizontal position.
FLOW
FLOW
A
B
8732-0005A
01EB
, 0005A
01FB
FLOW
8732-0005A01C