background image

This document may be photocopied for personal use. 

Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.

Join Emerson Retail Solutions Technical Support on Facebook. http://on.fb.me/WUQRnt

For Technical Support call 770-425-2724 or email [email protected]

The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or 

applicability. Emerson Climate Technologies Retail Solutions, Inc. and/or its affiliates (collectively “Emerson”), reserves the right to modify the designs or specifications of such products at any time without notice. Emerson does not 

assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any product remains solely with the purchaser and end-user.

026-4247 Emerson is a trademark of Emerson Electric Co. ©2017 Emerson Climate Technologies Retail Solutions, Inc. All rights reserved.

Document Part # 026-4247 Rev 4

Page 2 of 2

Termination should only be done at the two end points of the 
network. Set termination as appropriate as shown in 

Figure 4

.

Figure 4  - Gateway MODBUS Jumper Configuration

Mounting and Installation Tips

• Gateway Signal Range: 100-ft. radius.
• Mount the Gateway on the ceiling, parallel to the floor.
• Up to 99 Wireless Modules per Gateway.
• Position the Module with the Emerson logo pointing 

towards the Gateway for maximum performance.

• Try to avoid metal obstructions in the line of sight.
• Mount the Module in a location where 200 lux of light is 

visible to the solar cell for five (5) or more hours per day.

• If possible, commission a Module from its mounting 

location to verify good positioning.

• Check the signal strength on the E2 prior to permanently 

mounting the Modules.

• Gateways can be configured as a Repeater/Gateway in 

larger coverage areas or low cost Repeaters are available 
for applications not requiring additional Gateways.

Figure 5 - Overlapping Coverage Area

Set Up and Commissioning in E2

For complete instructions on set up and commissioning, refer to 
the Wireless User Manual

 

(

P/N 026-1734

).

Note: E2 Firmware version 3.08/4.08 is required

.

1. Set the desired COM port for MODBUS.

(

Menu

,

 7

,

 4

1

,

 C:3 Serial 

tab)

•    Baud: 19.2 Kbaud
•    Data Size: 8
•    Parity: Even
•    Stop Bits: 1

2. Add a Wireless Gateway in the Network Setup screen 

(

Menu

7

,

 7

,

 2

,

 C:3 ECT 

tab)

 

by changing the quantity of 

Wireless GW

 to 

1

.

3. After adding the Gateway, go to the Network Summary 

screen and select Wireless Gateway and then Commission 
(

Menu

,

 7

7

,

 1

,

 F4: Commission

).

4. Set the MODBUS address to 

247

 

to match the default 

address in the Gateway (this address is fixed in the 
Gateway). Enter 

247

 

or scroll down to 

247 

and press 

Enter

.

5. Press 

Enter

 to complete Commissioning.

Part Number

RF Description

814-3550

Wireless Gateway/Repeater 902MHz

814-3560

Wireless Repeater 902MHz, 24VAC

814-3570

Wireless Repeater 902MHz, 120VAC

814-3600

Wireless Module 902MHz with User Selected 
Inputs; Clean Mode

814-3653

Wireless Module 902MHz, 3 Temp; Clean Mode 
with Molex Connector

140-6802

Wall Mount 24VAC, 20VA Class 2 Transformer

Table 2- Ordering Information