This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
Join Emerson Retail Solutions Technical Support on Facebook. http://on.fb.me/WUQRnt
For Technical Support call 770-425-2724 or email [email protected]
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or
applicability. Emerson Climate Technologies Retail Solutions, Inc. and/or its affiliates (collectively “Emerson”), reserves the right to modify the designs or specifications of such products at any time without notice. Emerson does not
assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any product remains solely with the purchaser and end-user.
026-4247 Emerson is a trademark of Emerson Electric Co. ©2017 Emerson Climate Technologies Retail Solutions, Inc. All rights reserved.
Document Part # 026-4247 Rev 4
Page 2 of 2
Termination should only be done at the two end points of the
network. Set termination as appropriate as shown in
Figure 4 - Gateway MODBUS Jumper Configuration
Mounting and Installation Tips
• Gateway Signal Range: 100-ft. radius.
• Mount the Gateway on the ceiling, parallel to the floor.
• Up to 99 Wireless Modules per Gateway.
• Position the Module with the Emerson logo pointing
towards the Gateway for maximum performance.
• Try to avoid metal obstructions in the line of sight.
• Mount the Module in a location where 200 lux of light is
visible to the solar cell for five (5) or more hours per day.
• If possible, commission a Module from its mounting
location to verify good positioning.
• Check the signal strength on the E2 prior to permanently
mounting the Modules.
• Gateways can be configured as a Repeater/Gateway in
larger coverage areas or low cost Repeaters are available
for applications not requiring additional Gateways.
Figure 5 - Overlapping Coverage Area
Set Up and Commissioning in E2
For complete instructions on set up and commissioning, refer to
the Wireless User Manual
(
P/N 026-1734
).
Note: E2 Firmware version 3.08/4.08 is required
.
1. Set the desired COM port for MODBUS.
(
Menu
,
7
,
4
,
1
,
C:3 Serial
tab)
• Baud: 19.2 Kbaud
• Data Size: 8
• Parity: Even
• Stop Bits: 1
2. Add a Wireless Gateway in the Network Setup screen
(
Menu
,
7
,
7
,
2
,
C:3 ECT
tab)
by changing the quantity of
Wireless GW
to
1
.
3. After adding the Gateway, go to the Network Summary
screen and select Wireless Gateway and then Commission
(
Menu
,
7
,
7
,
1
,
F4: Commission
).
4. Set the MODBUS address to
247
to match the default
address in the Gateway (this address is fixed in the
Gateway). Enter
247
or scroll down to
247
and press
Enter
.
5. Press
Enter
to complete Commissioning.
Part Number
RF Description
814-3550
Wireless Gateway/Repeater 902MHz
814-3560
Wireless Repeater 902MHz, 24VAC
814-3570
Wireless Repeater 902MHz, 120VAC
814-3600
Wireless Module 902MHz with User Selected
Inputs; Clean Mode
814-3653
Wireless Module 902MHz, 3 Temp; Clean Mode
with Molex Connector
140-6802
Wall Mount 24VAC, 20VA Class 2 Transformer
Table 2- Ordering Information