Installation Instructions
Issue AB, March 22, 2012
Spec. No. 581127000 (Model 710
NPBA
)
Page 78
Chapter 4. Making Electrical Connections
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Battery Connections to Distribution Cabinet Battery Busbars
Danger:
Adhere to the “Important Safety Instructions” presented at the front of
this document.
Battery may be connected to the battery busbars located in the distribution cabinet, as
detailed in this section, depending on site requirements.
(4-Row Cabinet Shown,
Others Similar)
Battery
(Return Side)
Busbar
Battery
(Return Side)
Busbar
Battery
(Load Side)
Busbar
Battery
(Load Side)
Busbar
GND RTN
+24V SUPPLY
BATTERY AND BATTERY RETURN CONNECTIONS
3/8-16 Captive Nuts on 1
” Centers
(Customer must supply
additional hardware)
Maximum Lug Width: 1.88 inches
(unless otherwise noted).
Maximum Lug Width: 1.25 inches
(this location only).