Emerson 571-0066-00 Bulletin Download Page 6

 

 
 
 
 
 

AE8-1379 R2 

 

lockout  the  compressor,  and  after  the  issue  has  been 
resolved,  it  is  necessary  to manually  reset  the  module 
in order to clear the present alert code. 
 
The  primary  way  of  clearing  the  code  and  resetting  
the  alert  is  to  press  the  reset  button  located  on  the  
module.  Note:  Pressing  the  reset  will  require  a  pin  
or  mini/electronics  screwdriver.  This  button  must  be  
pressed and held for a minimum of one second for the  
module  to  be  reset.  Pressing  the  reset  button  clears  
the  immediate  lock  code  and  the  seven  day  operating  
history.  It  will  not  clear  the  permanent  module  history.  
In the case of the three-wire module, the codes can be  
reset  or  cleared  by  cycling  power  to  the  module. This  
can  be  done by  disengaging the Common (C) terminal.  
This will not clear the seven day operating history. 
 
Note: For the 571-0066-00 module, if a fault is present, it 
is  expected  that  the  thermostat  demand  will  remain 
present and the module will stay powered and function 
similar  to  the  571-0067-00  module.  If  the  thermostat 
demand  cycles  off,  then  the  571-0066-00  module  will 
reset and alert will clear. 

Module History Download 

The  CoreSense  Diagnostics  module  is  capable  of  
communicating  with  a  personal  computer,  tablet,  or  
laptop,  via  Emerson  Climate  Technologies  computer  
software interfaces (HVACR Fault Finder PC Edition) 

 

and  USB  connection  (TTL-232R-5V-WE),  in  order  to  
download  and  store  fault  history  and  module  operation  
time.  This  information  can  be  used  to  help  diagnose  
and  review  data  from  troubled  systems  in  the  field.  
HVACR    Fault    Finder    PC    Edition    kit  (9989-0099- 
01)  with  software  and  cable.  For  more  information,  
please  contact  your  Emerson  Climate  Technologies  
Application Engineer. 

Warranty Information 

Emerson    Climate    Technologies,    Inc.    warrants    its 
diagnostic  module  to  be  free  from  defects  in  materials 
and workmanship under normal use for a period of one 
year from the date of purchase or twenty months from 
manufacture,  whichever  comes  first.  During  this  period, 
Emerson  Climate  Technologies,  Inc.  will  replace  any 
defective diagnostic module without charge. 

 

For  more  information  on  product  warranty  please  visit 
EmersonClimate.com 

Support 

For    more    information    visit    EmersonClimate.com, 
or  contact  Emerson  Climate  Technologies,  Inc.  at 
1-888-EMR-9950.  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or 
services described herein or their use or applicability. Emerson Climate Technologies, Inc. reserves the right to modify the designs or specifications of such products at any time without  
notice. Emerson Climate Technologies, Inc. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any 
Emerson Climate Technologies, Inc. product remains solely with the purchaser and end-user.  

 

© 2015 Emerson Climate Technologies 

Summary of Contents for 571-0066-00

Page 1: ...ion 4 Compressor Protection 5 Module LED Description 5 Module Operation Code Description 5 Resetting Alert codes 5 Module History Download 6 Warranty Information 6 Support 6 Figures and Tables Two Wire Diagram Typical Cooling Application 7 Three Wire Diagram Typical Heat Pump Application 7 Three Wire Diagram Typical Cooling Application 7 Module Dimensions 8 Quick Reference Table 9 CoreSense Diagno...

Page 2: ...gly advised to follow these safety instructions SafetyIconExplanation DANGER WARNING CAUTION NOTICE CAUTION 2015 Emerson Climate Technologies DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol indicates a haza...

Page 3: ...ly approved refrigerants and refrigeration oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Personal safety equipment must be used Failur...

Page 4: ... continuously by R and C and is ideal for all packaged unit applications and for split systems applications where R and C are available at the outdoor unit See Figures 1 and 2 Product Specifications Operating Temp 40 to 150 F 40 to 65 C Storage Temp 60 to 175 F 49 to 80 C Supply Voltage 19 to 28VAC 48 to 62Hz 2015 Emerson Climate Technologies Working amperage for module 2 to 30A Maximum Power Cons...

Page 5: ...le will not lockout the compressor for this condition Code 2 Compressor Pressure Trips The module will flash yellow two times when the compressor operates from 12 seconds to 15 minutes 2015 Emerson Climate Technologies followed by a trip condition lasting longer than seven minutes When four consecutive Code 2 events are recorded the module will lockout the compressor and flash red two times Code 3...

Page 6: ... and store fault history and module operation time This information can be used to help diagnose and review data from troubled systems in the field HVACR Fault Finder PC Edition kit 9989 0099 01 with software and cable For more information please contact your Emerson Climate Technologies Application Engineer Warranty Information Emerson Climate Technologies Inc warrants its diagnostic module to be...

Page 7: ...o Wire Diagram HPCO LPCO T1 Defrost Board Indoor C Unit Y R ASC T2 Y C R Contactor Coil P PROT C Y R CoreSense Module Figure 2 571 0067 00 Three Wire Diagram Contactor Coil HPCO LPCO P PROT Indoor Unit C C Y Y R R CoreSense Module Figure 3 571 0067 00 Three Wire Diagram 2015 Emerson Climate Technologies 7 ...

Page 8: ...2 Current Sensor Opening Reset Bu on Yellow LED Red LED PROT Y 3 Wire Only C Data Port Not Present on 2 Wire R 3 Wire Only Y 2 Wire Only Figure 4 Dimensions are in Millimeters 2015 Emerson Climate Technologies 8 ...

Page 9: ...low Flash 5 Pressure switch cycling Compressor runs for 12 sec to 15 min followed by a compressor trip lasting between 35 sec to 7 min Locked rotor Compressor trips within a compressor run time of 12 sec and does not start within 35 sec Compressor moderate run trip Compressor runs for 15 min to 18 hrs followed by a compressor trip lasting longer than 7 min 4x consecutive Red Flash 3 or 10x total Y...

Page 10: ...ssor Yellow ALERT is running extremely long run Flash Code 1 cycles indicative of low capacity due to a system low side fault 3 Evaporator coil is frozen Check for low suction pressure Check for excessively low thermostat setting Check evaporator airflow coil blockages or return air filter Check ductwork or registers for blockage 4 Faulty metering device Check TXV bulb installation size location a...

Page 11: ...eck if system is overcharged with refrigerant Check for non condensable in system 3 Condenser coil poor air circulation dirty blocked damaged Red LOCK Short Cycling Compressor is 1 Thermostat demand signal is intermittent Flash Code 3 locked out after 10 consecutive 2 Time delay relay or control board defective Yellow Off short cycling events 3 If high pressure switch present go to Flash Code 2 in...