Resetting Power Module Variables
When power modules are replaced, you must reset Battery Life Remaining (shown in figure 34), which can be used for
scheduling maintenance of the power module. The counter can be reset using a Field Communicator or AMS Device
Manager. Resetting this value will also change the Power Module Date.
Field Communicator
Select
Online, Configure, Manual Setup, Power Module,
then
Reset Module Data
to reset Battery Life. Refer to the
Configure menu tree shown in figure 22.
Note
Reset Module Date
can also be accessed by selecting
Service Tools
,
Maintenance
, and
Power Module
.
AMS Wireless Configurator or AMS Device Manager
In AMS Device Manager select
Configure
,
Manual Setup
, then select
Reset Power Module Variables
from the Power tab, as
shown in figure 34, to reset the power module variables.
Figure 34. Resetting Power Module Variables
SELECT
RESET POWER
MODULE VARIABLES
BATTERY LIFE
REMAINING
POWER MODULE DATE (INDICATES
DATE OF POWER MODULE INSTALLATION)
1. A warning will be displayed, noting this should only be done when a new power module is installed. Select Next if
you have replaced the power module. Select Cancel if the power module has not been replaced.
2. Select Yes when asked if you want to continue.
3. Press Next on the status screen displayed.