background image

FB2100/FB2200 Flow Computer Coin Cell Battery Field Replacement Guide 

D301855X012 

November 2020

 

Removing/Replacing Batteries  

The coin cell SRAM backup battery preserves data in SRAM memory in the event of a power loss 
and provides backup power to the real-time clock.  

Refer to the table below for the correct field replacement kit part number. 

 
Item 

Field Replacement Kit 
Part Number 

Coin cell lithium battery for SRAM backup 

395620-03-1  

UL Kit File Number: E192567 

Ambient Temperature Range   

May be used up to a 

maximum

 ambient temperature of 80

°

C and a 

minimum

 ambient temperature 

of –40

°

C; refer to the data plate attached to the device.

 

Required Tools  

 

#2 Phillips-head screwdriver 

 

Hexagonal torque wrenches with 3mm and #1 Phillips-head bits. Ranges must include 4 to 6 
in-lbs (0.5 to 0.7 N-m). 

Electrical Ratings  

 

Input Voltage: 10.5 Vdc to 30 Vdc external supply (Max power at 10 watts) 

 

Restriction 

Hazardous area approvals require that any part replaced in the field be the exact same part (like for 
like). Upgrading or substituting different parts violates hazardous area certification. 

Important 

Use only accessories (batteries) supplied with the flow computer or sold by Emerson as spare parts 
for this flow computer. Substituting a part you obtain elsewhere (such as a battery) voids your 
approval certification.  

 DANGER 

EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous. 
Performing this operation in a hazardous area could result in an explosion.   

 

 DANGER

 

EXPLOSION HAZARD: Never open the enclosure in hazardous location. Opening the enclosure in 
a hazardous location could result in an  explosion.   

 

 WARNING 

EXPLOSION HAZARD – Substitution of any components may impair suitability for Class 1, 
Division 2. 

Summary of Contents for 395620-03-1

Page 1: ...puter Coin Cell Battery Field Replacement Guide D301855X012 November 2020 Remote Automation Solutions FB2100 FB2200 Flow Computer Coin Cell Battery Field Replacement Guide For Part Numbers Kits 395620 03 1 Coin Cell Battery ...

Page 2: ... Electrical Systems 29 CFR Part 1910 Subpart S dated April 16 1981 OSHA rulings are in agreement with the National Electrical Code You must also ground mechanical or pneumatic instruments that include electrically operated devices such as lights switches relays alarms or chart drives Important Complying with the codes and regulations of authorities having jurisdiction is essential to ensuring pers...

Page 3: ...e 4 to 6 in lbs 0 5 to 0 7 N m Electrical Ratings Input Voltage 10 5 Vdc to 30 Vdc external supply Max power at 10 watts Restriction Hazardous area approvals require that any part replaced in the field be the exact same part like for like Upgrading or substituting different parts violates hazardous area certification Important Use only accessories batteries supplied with the flow computer or sold ...

Page 4: ... Battery Field Installed Accessory Kit for Use in Class I Division 2 Groups A B C and D Flow Computer Coin Cell Battery Field Installed Accessory Kit Part No 395620 03 1 for Use with UL Listed Class I Division 2 Groups A B C D Model Series FB2100 and FB2200 A lithium coin cell battery provides backup power for the SRAM and the real time clock The SRAM backup battery can last for up to 10 000 hours...

Page 5: ...ery Field Replacement Guide D301855X012 November 2020 3 Loosen the Captive Fastening Screws Removing the CPU Enclosure Cover 3 Grasp the coin cell battery and with your fingernail in the groove of the top of the battery slide it out of its slot ...

Page 6: ...ent 4 Insert the new coin cell battery in the slot The negative side shiny with no writing on it must be facing outwards towards where the CPU enclosure cover would be 5 Reattach the cover of the CPU enclosure Tighten the captive fastening screws with a torque value of 4 to 6 in lbs 0 5 to 0 7 N m 6 Close the flow computer enclosure ...

Page 7: ...FB2100 FB2200 Flow Computer Coin Cell Battery Field Replacement Guide D301855X012 November 2020 5 ...

Page 8: ... services described or their use or applicability Remote Automation Solutions RAS reserves the right to modify or improve the designs or specifications of its products at any time without notice All sales are governed by RAS terms and conditions which are available upon request RAS accepts no responsibility for proper selection use or maintenance of any product which remains solely with the purcha...

Reviews: