background image

11

Emergency Mode

Applies only to Heat Pump Systems

Emergency Heat (System EM Position) 

bypasses the Heat 

Pump to use the heat source wired to terminal 

W/E, W2

 on 

the thermostat. 

EM

 is typically used when compressor opera-

tion is not desired, or you prefer back-up heat only.
1.  Press SYSTEM key to select 

EM

“EM Heat Mode” 

will 

flash on the display.

2. Press   to adjust thermostat setting above room tem-

perature. The Emergency heating system will begin to 
operate. The display will show 

“System On”

 flashing 

“EM 

Heat Mode” 

and “Heat” to indicate that the Emergency sys-

tem is operating.

3.  Adjust temperature setting to 3° above room temperature. 

Any additional stages of auxiliary heat should begin to 
operate and the display will show 

"System On +2"

.

4. Press   to adjust the thermostat below room tempera-

ture. The heating system should stop operating.

Cooling/Dehumidifier

1.  Press SYSTEM to select 

"Cool"

.

2. Press   to adjust the thermostat setting below room tem-

perature. The blower should come on immediately on high 
speed, followed by cold air circulation. The display should 
show "

System On"

. If the setpoint temperature display is 

flashing, the compressor lockout feature is operating (see 
Configuration menu, item 11).

3.  Adjust temperature setting to 3° below room temperature. 

The second stage cooling should begin to operate and the 
display should show 

"System On +2"

.

4. Press   to adjust the temperature setting above room 

temperature. The cooling system should stop operating.

To check the dehumidifier when 

System On

 appears and 

the cooling system is running press 

HUMIDITY

* button once. 

Press 

 to adjust the humidity 2% or more below the room 

humidity level setpoint range. 

DeHum On

 will appear indicat-

ing it is calling for the dehumidification.
If the room humidity is lower than the adjustment range, press 

 to 40% and hold it for four seconds. This will force the 

De-

Hum On

 for one complete cooling cycle to test the dehumidi-

fication equipment.
After adjusting the humidity setting the display will return to 
temperature in approximately 10 seconds. To switch the dis-
play back to temperature immediately after adjusting humidity 
setting press 

HUMIDITY

 again.

*Note: 

If 

Auto Schedule

 is displayed instead of 

Humidity

Auto Schedule

 must be turned off in the Configuration Menu.

Choose the Fan Setting (Auto or On)

Fan 

Auto

 is the most commonly selected setting and runs the 

fan only when the heating or cooling system is on. 

To prevent compressor and/or property damage, if the 
outdoor temperature is below 50°F, DO NOT operate 
the cooling system.

CAUTION

!

Fan 

On

 selection runs the fan continuously for increased air 

circulation or to allow additional air cleaning.
Tip: Running the fan more frequently will increase your 

energy consumption. Most systems use a 1/2 or 1/3 HP 
electric motor to power the fan.

Choose the System Setting

(Cool, Off, Heat, Em, Auto)

Press the SYSTEM key to select:

Cool: 

Thermostat controls only the cooling system.

Off: 

Heating and Cooling systems are off. 

Heat: 

Thermostat controls only the heating system.

Em: 

Setting is available only when the thermostat is config-

ured in HP1 or HP2 mode.

Auto: 

Auto Changeover is used in areas where both heating 

and cooling may be required on the same day. 

AUTO

 allows 

the thermostat to automatically select heating or cooling 
depending on the indoor temperature and the selected heat 
and cool temperatures. When using 

AUTO

, be sure to set the 

Cooling temperatures more than 1° Fahrenheit higher than 
the heating temperature.

Manual Operation for

Non-Programmable Mode

Press the SYSTEM key to select 

"Heat"

 or 

"Cool"

 and use

the keys to adjust the temperature to your desired setting. 
After selecting your desired settings you can also press the 
SYSTEM key to select 

AUTO

 to allow the thermostat to auto-

matically change between 

"Heat"

 and 

"Cool"

.

Manual Operation (Bypassing the Program)

Programmable Mode

Manual operation will bypass the program and allow you to 
adjust the temperature as you desire. The temperature you 
set in 

Hold

 will be maintained indefinitely. Press 

 or 

 to 

adjust the temperature. The HOLD key will appear. Press the 
HOLD key. "

Hold At"

 will appear next to the setpoint tem-

perature and the thermostat will maintain the new setpoint 
temperature until 

Run Schedule

 is pressed to resume pro-

gram operation.

Program Override (Temporary Override)

Press 

 or 

 keys to adjust the temperature. This will over-

ride the temperature setting for a (default) four hour override 
period. The override period can be shortened by pressing   
or lengthened by pressing  . Program Override period can 
range from 15 minutes to 7 days.

Example: 

If you turn up the heat during the morning program, 

it will be automatically lowered later, when the temporary hold 
period ends. To cancel the temporary setting at any time and 
return to the program, press 

Run Schedule

.

If the SYSTEM key is pressed to select 

AUTO

 the

thermostat will change to 

"Heat"

 or 

"Cool"

, whichever 

ran last. If it switches to 

"Heat"

, but you want 

"Cool"

, or it 

changes to 

"Cool"

, but you want 

"Heat"

, press both keys 

simultaneously to change to the other mode.

 

  OPERATING YOUR THERMOSTAT

Summary of Contents for 1F95-1291

Page 1: ...ury However this prod uct may replace a product that contains mercury Mercury and products containing mercury must not be discarded in household trash Do not touch any spilled mercury Wearing non absorbent gloves clean up any spilled mercury and place in a sealed container For proper disposal of a product containing mercury or a sealed container of spilled mercury place it in a suitable shipping c...

Page 2: ...e Power Stealing Switches Fig 1 should be left in the On position for most systems The information in the following table details the thermostat power method and switch options WARNING Thermostat installation and all components of the control system shall conform to Class II circuits per the NEC code INSTALLATION Figure 1 Thermostat Base Multi Stage 1F95 1291 2 AA Batteries Power Stealing Switches...

Page 3: ...ency Mode 1st stage Note Dual Fuel option de energizes Heat mode stage 1 compressor when auxiliary heat is energized Heat mode 3rd stage Emergency Mode 1st stage Note Dual Fuel option de energizes Heat mode stages 1 and 2 both compressors when auxiliary heat is energized Heat mode 4th stage Emergency Mode 2nd stage Note Dual Fuel option de energizes Heat mode stages 1 and 2 both compressors when a...

Page 4: ...tem HOT NEUTRAL 120 VAC TRANSFORMER HM 24 VAC Humidifier System R Figure 7 Typical Wiring for 24V Humidifier System Dehumidification wiring without an electronically controlled variable speed blower system for single stage compressor system only HM DHM Humidification Terminal Energizes on call for heat if Humidity setpoint is above room humidity Can also be used to provide humidification independe...

Page 5: ... 3 7 3 8 3 9 3 20 21 2 1 11 12 10 16 17 9 8 18 14 13 4 19 15 A steady Cool Savings display indicates the feature is enabled in the installer menu A flashing Cool Savings display indicates the feature is active 16 Remote indicates that the indoor remote temperature sensor is being accessed Outdoor Remote indi cates the outdoor remote temperature sensor is being accessed 17 Display time remote tempe...

Page 6: ... available if 4 is 0 8 FA Heat Cr SL Selects Adjustable Anticipation cycle rate Heat 9 FA Cool Cr SL Selects Adjustable Anticipation cycle rate Cool 10 FA Cr AU Em SL Selects Adjustable Anticipation cycle rate auxiliary This item is only to appear if HP1 or HP2 is selected above 11 OFF CL On Selects Compressor Lockout 12 On dL OFF Selects Continuous Display backlight 13 0 Temperature 5 LO to 5 HI ...

Page 7: ...h the program setpoint at the time you specify Example The heating program is 65 F at night and 70 at 7 AM If the building temperature is 65 F the difference is 5 F Allowing 5 minutes per F rise the thermostat set point will change to 70 at 6 35 AM Cooling allows more time per F because it takes longer to reach temperature 8 9 10 Cycle Rate Selection The factory default setting is fast cycle FA Cr...

Page 8: ... to 6 When an offset starts or is active Cool Savings will flash on the display The principle of this energy saving feature takes advantage of the long air conditioning run times lowering the indoor humidity allowing a slightly higher temperature to feel comfortable As the peak load subsides this feature also takes advantage of the air conditioner s increased capacity under more efficient conditio...

Page 9: ... stage separation This adjust ment allows a small change in the operation of your heat INSTALLER CONFIGURATION MENU pump system versus your auxiliary system relative to the thermostat adjustment The higher the number the sooner the auxiliary stage energizes for better comfort The lower the number the longer period of time before auxiliary is energized for more economy Note This setting is not minu...

Page 10: ...ded maintenance schedule When Change UV Lamp is displayed you can clear it by pressing Clean Display 46 47 Change Humidifier Pad This feature allows the thermostat to display the words Change Pad after a set time of humidifier operation This is a reminder to main tain or clean your humidifier The factory set interval for Change Pad to be displayed is 100 hours of humidifier operation This should b...

Page 11: ... and or property damage if the outdoor temperature is below 50 F DO NOT operate the cooling system CAUTION Fan On selection runs the fan continuously for increased air circulation or to allow additional air cleaning Tip Running the fan more frequently will increase your energy consumption Most systems use a 1 2 or 1 3 HP electric motor to power the fan Choose the System Setting Cool Off Heat Em Au...

Page 12: ...u wish to copy to is flashing 5 Press Copy Copy will disappear the day you copied from will disappear and the day s you copied to will be on 6 If you wish to copy this same program into other days press Copy and repeat steps 3 4 and 5 7 Press Run Schedule to return to normal operation Fill in the blank schedule on the next page then Enter the Heating Program 1 Press the Menu key and then press Set...

Page 13: ...of the week You can eliminate these two program periods in the configuration menu reference 5 if the building is occupied all day Day period will change to 6 00 AM and 70 and can be programmed as required Wake Up Morning Leave For Work Day Return Home Evening Go To Bed Night Heating Program 6 00 AM 70 F 8 00 AM 62 F 5 00 PM 70 F 10 00 PM 62 F Cooling Program 6 00 AM 75 F 8 00 AM 83 F 5 00 PM 75 F ...

Page 14: ...n the terminal block allow connection of the remote sensor The thermostat must have 24 VAC Common connection to terminal C for the remote sensor to operate The remote sen sor can be enabled or disabled in the Installer Configuration menu item 29 When remote sensor Remote is selected Off factory de fault no remote sensor is enabled When remote sensor is selected On the next step is to select the re...

Page 15: ... the dual fuel temperature setpoint menu item 33 can be set to a temperature of 5 through 50 When outdoor remote sensor is not installed a software logic based dual fuel number menu item 34 from 01 to 09 can be selected A higher temperature or dual fuel setting will provide a smaller stage separation between the heat pump and Aux to give more comfort A lower temperature or number will provide a la...

Page 16: ... connection to verify they are not shorted or touching together No bare wire should stick out from under terminal block Try resetting the thermostat as de scribed above If the condition persists the manufacturer of your system or service person can instruct you on how to test the Heat Cool system for correct operation If the system operates correctly replace the thermostat Thermostat Setting Therm...

Reviews: