INSTALLER/CONFIGURATION MENU
To enter the menu: Press the
Menu
touch key . Press and hold for 5 seconds the
Installer Config
touch key . This displays
screen reference #1 in the table below . Screen Reference numbers appear in top right corner of display . Press
to advance
to the next menu item or
to return to a previous menu item . Press or to change a menu item option . Shaded items are
not available if selected for Non-Programmable .
CONFIGURATION MENU
Screen
Reference
Number
SS1
MS2
HP1
HP2
Press
key
Displayed
Factory
(Default)
Press
or
to select from
listed options
Comments
1
MS 2
HP 1, HP 2, SS 1
Selects Multi-Stage (MS2, No Heat Pump), Heat Pump 1
(HP1, 1 compressor), Heat Pump 2 (HP2, 2 compressor
or 2 speed compressor), or Single Stage .
2
(GAS)
ELE
GAS setting: furnace controls blower .
ELE setting: thermostat controls blower .
3
0b (0)
b
Selects Reversing Valve (This item is only to appear if HP1 or HP2
is selected above .)
4
Days,
(7) P
5
or
0
Programs per week . (7 days, 5-1-1 days or non-programmable)
5
Cool-Off-
Heat-Auto
Cool-Off-Heat, Heat Off,
Heat, Cool-Off, Auto Off
System switch configuration in non heat pump mode .
Cool-Off-Heat-
Em-Auto
Cool-Off-Heat-Em,
Off-Em-Auto
System switch configuration, heat pump mode .
6
(On)
E
OFF
Selects Energy Management Recovery . Not available if 4 is 0
7
(FA) Heat, Cr
SL
Selects Adjustable Anticipation, cycle rate, Heat
8
(FA) Cool, Cr
SL
Selects Adjustable Anticipation, cycle rate, Cool
9
(FA) Cr/AU, Em
SL
Selects Adjustable Anticipation, cycle rate auxiliary, (This item is
only to appear if HP1 or HP2 is selected above) .
10
(OFF)
CL
On
Selects Compressor Lockout .
11
(On)
dL
OFF
Selects Continuous Display backlight .
12
(LO)
dL
HI
Selects Backlight Intensity .
13
0
(Temperature)
5, LO to 5, HI
Selects Adjustable Ambient Temperature Display [range -5 (LO) to
+5 (HI)] .
14
°F
°C
Selects °F/°C Display (temperature units in Fahrenheit or Celsius) .
15
(On)
b
OFF
Selects audible Beeper On/Off .
16
(On)
dS
OFF
Selects Daylight Saving Time calculation .
17
(On) Heat,
AS
OFF
Selects Automatic Schedule for comfort temperature Programming,
heat mode . Not available if 4 is 0
18
(On) Cool,
AS
OFF
Selects Automatic Schedule for comfort temperature Programming,
cool mode . Not available if 4 is 0
19
(OFF)
CS
On
Selects Cool Savings Feature On of Off .
20
CS
Cool Savings
(3)
1-2-3-4-5-6
Selects amount of Cool Savings adjustment .
21
(OFF)
CO
On
Selects Compressor Optimization (not available on earlier models)
22
(99) Heat,
HL
62-98
TEMPERATURE LIMIT, HEAT (max . heat set point) .
23
(45) Cool,
LL
46-82
TEMPERATURE LIMIT, COOL (min . cool set point) .
24
OFF,
Keypad Lockout
L
(total),
P
(partial),
Temperature Limit
(limited temperature range)
Selects Keypad Lockout .
25
000
001-999
Selects Keypad Lockout Combination (active only if keypad Lockout
is selected) .
26
MS2
(On) Heat, FS
OFF
Fast second stage of heat (not available if SS1 is selected above) .
27
MS2
HP2
(On) Cool, FS
OFF
Fast second stage of cool (not available if SS1 or HP1
is selected above) .
28
Remote (OFF)
On
Remote temperature sensor, enable/disable .
29
Remote, In
Outdoor Remote
Remote temperature sensor (Indoor/Outdoor) .
30
(On) LS
OFF
Local temp . Sensor enable/disable (only when Indoor Remote is
selected On) .
31
(OFF) dF
On
Selects Dual Fuel feature On or OFF (this item appears if HP1 or HP2
is selected above) .
32
(35) dF
-5 - 50
Selects Dual Fuel setpoint (°F), dF selected On with outdoor sensor
available .
33
(05) dF
0 - 09
Selects Dual Fuel setting using software logic, dF selected On with no
outdoor sensor .
5
Summary of Contents for 1F95-1280