White-Rodgers 70 Series Thermostat Line Extension
20
Menu
Description
Setting
Options
30 CR
Heat Cycle Rate (how often the heat will turn on)
MEd
SLOW – slow
MEd – medium
FAS – fast
32 CR
Aux Cycle Rate (how often the auxiliary heat will turn on)
MEd
SLOW – slow
MEd – medium
FAS – fast
35 CR
Cool Cycle Rate (how often the cooling will turn on)
MEd
SLOW – slow
MEd – medium
FAS – fast
50 CL
Compressor Lockout (protects the compressor from short cycling)
OFF
On – 5-minute display
OFF – no delay
60 dF
Duel Fuel Logic (turn On when using gas as the auxiliary heat
source)
OFF
On – gas auxiliary heat
OFF – electric auxiliary heat
65
Maximum Heat Limit (maximum set point for heat mode)
99
47 to 99
66
Minimum Cool Limit (minimum set point for cool mode)
45
45 to 97
74
Schedule Type (set as either 7-Day, 5-1-1 Day or Non-
Programmable)
5
7 – 7 day
5 – 5-1-1 day
0 – Non-Programmable
76 E
Early Start (starts heating or cooling early so your programmed
temperature is reached by the programmed time)
Off
On – start early
OFF – start at program
period time
79
Fahrenheit or Celsius
°F
°F – Fahrenheit
°C - Celsius
81
Temperature Display Adjustment (adjust the displayed “Room
Temperature”)
0
-5 to +5
83 dL
Continuous Display Light (keep the backlight always on – “C” wire
required)
OFF
On – always on
OFF - momentarily
86
Change Air Filter (set up a monthly reminder)
OFF
1 to 12 – reminder time
OFF – no filter reminder
Technical Details - Installer Menu Options