REAL TIME CLOCK SETTINGS

1.   In the main interface, click the button “ ” to enter the real-time 

clock setting interface: 

 - Press the button “ ” again to enter hour setting  

(“HH” zone is flashing) 

- Press the button “

” or “

” to adjust hour to the real time 

- Press the button “ ” again to confirm the hour and enter the 

minute setting (“MM” zone is flashing) 

- Press the button “

” or “

” to adjust minute to the real time 

- Press the button “ ” again to confirm the minute 

- Press “ ” to confirm time clock setting and return to the main 

interface.

2.   In the real-time clock setting interface, no button operation for 

more than 5 seconds, the current real-time clock setting value  

will be confirmed and returned to the main interface.

 TIME PERIOD SETTINGS

1.   The three default time periods are 09:00-17:00, 00:00-18:00, 

00:00-00:00. 

2.   In the main interface, press the button “ ” for 3 seconds to enter 

or exit time period setting. 

3.   In the time period setting interface, click the button “ ” to switch 

the hour and minute of the start time and end time, also click the 

button “ ” to switch time period 1, 2 and 3. 

4.   The value is flashing when switching to the corresponding value 

of the time period. Meanwhile the icon “ON” or “OFF” is flashing, 

Press "

” or “

” to increase or decrease the corresponding value. 

Press the button “

” or no operation in 15 seconds, the setting 

will be saved and the controller will return to the main interface.

5.   In the time period setting interface, the corresponding icon ON 

will be displayed if the corresponding time period is set, the  

corresponding icon OFF will be displayed if the corresponding 

time period is not set.

6.  The system will only work during the time period if it is set.
7.   If the start time is same as the end time, it will canceling this timing 

period. 

8.   If all 3 timed periods are canceled, system is allowed to work 

anytime. 

9.   If the start time of time period is later than the end time, the end 

time is considered to be the 2nd day.

ELECTRIC HEATER CONTROL

BOOSTER MODE

1.   To turn on/off electric heating element Press both buttons“

”+“

” simultaneously for more than 3 seconds.

2.   The electric heating element will heat the water to the set  

temperature.

3.   The icon "

" keeps constantly bright during Booster mode,  

also the heat pump will stop running.

ELECTRIC HEATER MODE

1.   If the following issues happen, the electric heating element will  

be activated if water requires heating:

  High pressure alarm

  Low ambient temperature mode 

  High ambient temperature mode 

  High gas exhaust temperature alarm 

  Gas exhaust temperature sensor failure 

  Gas return temperature sensor failure

2.   Under manual mode for water temperature setting, the working of 

electric heating element is decided by water setting temperature 

and dead-band temperature.

3.   Under Auto mode for water temperature setting, the working of 

electric heating element is decided by water temperature and 

ambient temperature, please see following table:

A.T.(°C)

A.T≤15

15

<A.T≤20

20

<A.T≤25

25

<A.T≤30

30

<A.T≤35

35

<A.T≤38

A.T≥38

W.T.(°C)

55+F05

53+F05

50+F05

48+F05

46+F05

44+F05

42+F05

HIGH TEMPERATURE MODE

1.   When ambient temperature ≥ 43°C (it can be adjusted by F86), the 

heat- pump will stop running. The system will activate the electric 

heating element to heat the water instead until the temperature 

recovers to the normal range.

2.   When ambient temperature ≤ 41°C, the electric heating element 

will stop running. The system will activate the heat pump and run in 

standard conditions..

3.   Under low temperature mode, the working of electric heating 

element is decided by water setting temperature and dead-band 

temperature.

LOW TEMPERATURE MODE

1.   When ambient temperature ≤ -7°C (it can be adjusted by F10), the 

heat pump will stop running, also the electric heating element will 

start to work if necessary.

2.   When ambient temperature is ≥ -5°C the electric heating element  

will stop working. The heat pump will run if necessary.

3.   Under low temperature mode, the electric heating element starts 

or stops working which is decided by water setting temperature 

and dead-band temperature.

CONTROLLER INSTRUCTIONS

Summary of Contents for EE-HWS-SSHP-200

Page 1: ...d Energy This leaflet contains important information on the correct installation and operation of your heat pump water heater PACKING LIST 1 User manual 1 Heat pump unit 1 Water tank unit 1 TPR valve...

Page 2: ...ments 6 Electrical work must be insulated and compliant with electrical technical standards 7 The unit must be powered for 3 4 hours before use INSTALLATION SPACE 1 Check space for maintenance before...

Page 3: ...inlet and outlet pipe for hanging Refer to the Hoisting Heat Pump diagram PLUMBING CONNECTION Connecting water inlet and outlet pipes To house Hot water To drain Cold water Control panel Water temper...

Page 4: ...0mm female thread 2 The hot water supply should be connected to a 20mm socket 3 To ensure thermal efficiency all hot water lines and connections must be insulated with a minimum 13mm closed cell insul...

Page 5: ...nection Wiring must be conducted by a professional installation technician in accordance with the circuit diagram The power and signal line layout should be neat and not in contact with each other or...

Page 6: ...Display Timer mode ECO mode Constantly bright In the range of timer period Flashing Set starting time for timer mode Constantly bright Out of the range of timer period Flashing Set ending time for ti...

Page 7: ...inspection of controller screen System is OFF make sure the system connects with power supply less than 5 minutes before operation Press all 4 buttons simultaneously for 5 seconds to restore the fact...

Page 8: ...y ELECTRIC HEATER CONTROL BOOSTER MODE 1 To turn on off electric heating element Press both buttons simultaneously for more than 3 seconds 2 The electric heating element will heat the water to the set...

Page 9: ...ng element 16 0 OFF 1 ON Compressor running time before defrost 17 Real accumulated time Back up linked switch 18 0 open 1 close Programme version 19 Show real version No MANUAL STERILIZATION 1 If the...

Page 10: ...sorb temperature sensor and outlet water temperature sensor return water temperature sensor are faulty CONTROLLER INSTRUCTIONS THE ALARM LOW PRESSURE FAULT 1 If the compressor starts running for 5 min...

Page 11: ...red Regularly check the reliability of the electrical components Change any faulty or unreliable components After a long period of operation there will be a build up of calcium oxidized or other miner...

Page 12: ...d inlet or compressor suction pipe is blocked expansion valve unadjusted or failed The refrigerant is not enough in the sytem Adjust suitable overheat temperature examine whether there is Fluo rine le...