background image

© 2012, Elvaco AB. All rights reserved. The docum entation and product are provided on an “as is” basis only and m ay contain 
deficiencies or inadequacies. Elvaco AB takes no responsibility for dam ages, liabilities or other losses by using this product. No part of the 
contents of this m anual m ay be transm itted or reproduced in any form  by any m eans without the written perm ission of Elvaco AB. 
Printed in Sweden 

M -Bus Splitter Quick manual A4 English

 

Docum ent id:

 1090049 

Version:1.0

 

 

Set t ings 

 

Speed M-Bus OUT1 

Jum per 1, yellow  

M ode 

Descript ion  

V isual  

Jumper on 

2400 baud 

   

 

Jumper off 

300 baud 

 

 

Scanning speed M-Bus IN 

Jum per 2, blue 

M ode 

Descript ion  

V isual  

Jumper on 

2400 baud 

   

 

Jumper off 

300, 2400 baud 

 

 

Readout interval M-Bus IN 

Jum per 3 and 4, black 

M ode 

Descript ion  

V isual  

Jumper off 
Jumper off 

1 minute 

 

 

 

 

Jumper off 
Jumper on 

5 minutes 

 

 

   

 

Jumper on 
Jumper off 

30 minutes 

   

 

 

 

Jumper on 
Jumper on 

12 hours 

   

 

   

 

Speed M-Bus OUT2 

Jum per 5, red 

M ode 

Descript ion  

V isual  

Jumper on 

2400 baud 

   

 

Jumper off 

300 baud 

 

 

LED indicat ions 

M-Bus IN 

LED indications for M-Bus IN 

M ode 

Descript ion  

V isual  

4 short flashes 
every 3 seconds 

Start-up/ 
charging 

 

 

Short flash 
every second  

Readout 

 

 

Off 

No meter 
installed/error on 
the bus 

 

 

1 flash every 12 
seconds 

1 installed meter 

 

2 flashes every 
12 seconds 

2 installed 
meters 

 

3 flashes every 
12 seconds 

3 installed 
meters 

 

4 flashes every 
12 seconds 

4 installed 
meters 

 

M-Bus OUT 2 

LED indications for M-Bus OUT 2 

M ode 

Descript ion  

V isual  

4 short flashes 
every 3 seconds 

Start-up/ 
charging 

 

 

off 

Error on the bus 

 

1 flash every 12 
seconds 

Normal 
operation 

 

2 flashes every 
12 seconds 

Communication 

took place last 
minute  

 

M-Bus OUT 1 

LED indications for M-Bus OUT 1 

M ode 

Descript ion  

V isual  

4 short flashes 
every 3 seconds 

Start-up/ 
charging 

 

 

off 

Error on the bus 

 

1 flash every 12 
seconds 

Normal 
operation 

 

2 flashes every 
12 seconds 

Communication 
took place last 
minute  

 

Technical specif icat ions 

M echanics

 

Material 

Polycarbonate 

Dimensions 

75x55x110 mm  

Weight 

100 g 

Mounting 

DIN-rail or wall mounting 

Connect ions an d int erf ace

 

Connection 

M-Bus screw terminal 

M -Bus 2-w ire int erf ace - m ast er port

 

Nominal voltage 

23-27 VDC 

M-Bus baud rate 

300, 2400 Bit/s 

Max. connected meters  

Scanning range 

0-250 (multiple slave), 254 
(single slave) 

Scanning interval 

1 min, 5 min, 30 min or 60 min 

Standards 

EN 13757 

M -Bus 2-w ire int erf ace – slave port s 

Nominal voltage 

21-42 VDC (M-Bus standard) 

Power consumption 

2T-6T (3-9 mA) 

M-Bus baud rate 

300, 2400 Bit/s 

Standarder 

EN 13757 

M-Bus commands 

SND_NKE, REQ_UD2 

Ext ernal pow er  

Nominal voltage 

24-35 VAC or 30-40 VDC 

Power consumption 

25 mA 

User int erf ace

 

Operation indication 

See LED indications 

Ot her

 

Other 

Independent of meter 
manufacturer, auto configuring 

Ordering inf orm at ion 

Product  

Part  num ber  

Descript ion  

M-Bus Splitter

 

1050013 

Share up to 4 M-Bus 
slaves 

Cont act  inf orm at ion 

Elvaco AB  
Headquarter 

Phone: +46 300 30250 
Fax: +46 300 18440 
E-mail: [email protected]  

 

 
Teknikgatan 18 
43437 Kungsbacka 

SWEDEN 
 

Elvaco AB  
Technical support 

Phone: +46 30 0 434 300  

E-mail: [email protected]  
Online: w w w.elvaco.com  

 

 

 