![Eltek Valere UNV-F 2.5 User Manual Download Page 9](http://html1.mh-extra.com/html/eltek-valere/unv-f-2-5/unv-f-2-5_user-manual_2397270009.webp)
DC/AC Inverter
UNV-F
User Manual
Page 9 (28)
©2009. ELTEK VALERE DEUTSCHLAND GmbH.
UM_UNVF_ E_R2.0
3.3 Electrical Connectors
3.3.1 Electrical Connector X1 for UNV-F 2.5 – 3.3kVA, UNV60-5.0F and UNV110-5.0F
X1 (HAN-K4/8) socket outlet (DC input voltage / AC output voltage and signalling):
X1/Pin
Designation
1
DC input, plus pole
2
AC output, neutral conductor
3
DC input, minus pole
4
AC output, phase L1
5 ---
6
SYNC-GND (synchronous bus ground)
7 SYNC-SIG
*
(synchronous bus 50Hz-signal)
8 SYNC-STAT
**
(synchronous bus state lines)
9 ---
10
Collective failure COM
***
11
Collective failure OK (normally open=NO)
12
Collective failure error (normally closed=NC)
The maximum allowed load for the relay contacts is:
@ V= 110V / I< 0.45A
DC
@ V
60V
DC
/ I< 1A
DC
*In parallel operation the contacts SYNC – GND and SYNC – SIG of each inverter have to be wired.
**In operation with an UNB it is necessary to interconnect the synchronization bus (contacts SYNC – GND, SYNC
– SIG and SYNC – STAT) between the inverter(s) and the UNB.
***Potential free relay contact with safe electrical separation to the AC and DC side; in case of failure COM and
NC are closed.