enCore FC1
Operating Instructions
Page 38 of 97
5 Assembly Instructions
The FC1 is provided for assembly within a 19" cabinet, and is available in
either a 1/3 overall width or 1/2 overall width model. Compliance with the
device's installation depth of 170 mm (with plugs approx. 220 mm) is
necessary so the connection terminals located on the rear of the device
remain accessible.
The FC1 must be installed in an Ex free plant room (electrical
room) outside of Ex zones 0, 1 and 2, in accordance with pro-
tection class IP 20.
It is recommended that the FC1 be installed in a swivel frame.
5.1 Line Connection
WARNING!
Risk of explosion
A risk of explosion exists if lines are connected to the
ExMFE5 board while the device is connected to the power
supply!
Only connect transmitter, pulse and signal lines to the ExMFE5
board when power supply of the FC1 is disconnected completely.