EK280
Application Manual
104
7.3.9
FE260 with RS232 interface card
RS232 interface,
e.g. the COM port of a PC
RS232 module 73016593 V1.1
Jumper J1 in position "RS232"
Figure 17: RS232-Adapter in the FE260
GND
GND
(n.c.)*
RI/DSR
(n.c.)*
DTR/RTS
(n.c.)*
DCD/CTS
RXD
TxD
TXD
RxD
* (n.c.) = not connected
This interface card is used to communicate with PCs and other serial interface devices.
7.3.9.1 Preparation
Initial conditions:
Place jumper J1 into the "RS232" position. (see Figure 17)
The FE260 is connected and configured as described in chapter 7.3.1.
The serial communication link to the PC or other device is set up.
7.3.9.2 EK280 Parameterization
i
For parameterization of the EK280 you will require a connection cable for the optical interface as
well as the enSuite application, which can be downloaded for free at www.elster-instromet.com.
a) Closing the time windows
In order that the parameterization works correctly the time windows 5 and 6 must be closed. To do this:
Connect a PC or laptop with enSuite installed to the EK280 optical interface using the connection
cable.
Start enSuite and set up the communication link to the EK280. (see chapter 3.1 "Setting up the
communication link to the EK280 via optical interface", page 15)
Select "
Navigation
" on the left-hand side and then "
Parameterize online
" at the bottom of the
navigation window.
In the top of the device window open the path "
Parameter
" > "
Interfaces
" by clicking on the relevant
plus signs, and then select "
Call time windows
".
In call windows 5 and 6 set start and end to the same value for each one and then select the
"Transfer changes to device" icon at the top of the enSuite window.
Then wait a minute, for any communications activity in progress on the EK280 to be safely stopped.