WARNING

!

Use authorized utility procedures to install and service metering equipment. Dangerous voltages with high current 
capabilities are present. Equipment damage, personal injury, or death can result if safety precautions are not followed.

The AGI RLC polyphase interrupter for use with an A3 ALPHA meter

1

 contains the following items:

AGI RLC enclosure assembly

optional antenna cable, 3-foot or 10-foot (may be shipped inside enclosure assembly)

3-foot or 10-foot service control cable (may be shipped inside enclosure assembly)

1

3-foot or 10-foot contactor status cable (may be shipped inside enclosure assembly)

1

Mounting bracket (optional)

Mounting bracket installation materials (may be shipped with mounting bracket)

Contact Elster’s support line at +1 800 338 5251 if you do not have all the required materials.

Before you install

WARNING

!

Use authorized utility procedures to install and service metering equipment. Dangerous voltages with high current 
capabilities are present. Equipment damage, personal injury, or death can result if safety precautions are not followed.

NOTICE

Be sure to remove power before beginning the installation of the polyphase service control device. Removing the meter 
from the socket 

does not necessarily

 

remove power.

Unpack all the materials, and be sure that you have all the components before installing the polyphase service control 
device in the field.

Referencing Figure 1, you must attach the mounting bracket to the enclosure using the mounting bracket installation 
materials, torquing to 20 foot-pounds (±0.5 foot-pounds). Also, your polyphase service control device may be equipped 
with an optional external antenna. If the unit is not using the optional external antenna, the hole seal will be inserted 
instead.

1

Cable length is specified at the time of order.

Summary of Contents for AGI RLC

Page 1: ...upled with an A3 ALPHA meter1 equipped with either an EnergyAxis System integrated wireless LAN mesh radio or an integrated wireless WAN option board the AGI RLC can be controlled using the EnergyAxis System Additionally the A3 ALPHA can provide essential metering and monitoring for your remote polyphase loads While the AGI RLC polyphase interrupter can be coupled with another controller such as a...

Page 2: ...ave all the required materials Before you install WARNING Use authorized utility procedures to install and service metering equipment Dangerous voltages with high current capabilities are present Equipment damage personal injury or death can result if safety precautions are not followed NOTICE Be sure to remove power before beginning the installation of the polyphase service control device Removin...

Page 3: ...rupter assembly isometric view 120 A version shown 200 A is similar HAZA RD O U S VO LTA GE S ON ELEC TR IC ALCO MPO N E N T S C ANSH O CK BU R N OR C AUSED EATH Antenna Enclosure Back panel optional Hole seal optional Mounting bracket may be shipped separately ...

Page 4: ... for the source terminals is 60 VA 7 Double pole circuit breaker 8 Manual switch to locally restore service 9 Terminal block with two aux control terminals and two 120 V source terminals 10 Surge protector 11 Control connector 12 Enclosure latch lockable Auxiliary switch for LED control Eaton part number C25HNY5 Part part number subject to change without notice Eaton part number C25KNY9 Part part ...

Page 5: ...3 LED operation 200 A version shown 120 A version indicators are identical 1 2 CLOSED OPEN 1 Red LED Indicates contactor is closed Power should be present at load 2 Green LED Indicates contactor is open Power should be absent from load ...

Page 6: ...IL42 4034D February 2012 6 Figure 4 AGI RLC wiring diagram ...

Page 7: ...GI RLC polyphase interrupter assembly dimensions 120 A version 14 40 0 39 diameter 0 39 diameter 2 50 5 25 13 00 8 20 4 50 3 50 2 inch conduit hole both sides 5 00 3 88 10 11 Approximate dimensions in inches 17 50 16 60 2 inch conduit hole ...

Page 8: ...LC polyphase interrupter assembly dimensions 200 A version Approximate dimensions in inches 20 00 0 53 diameter 0 53 diameter 11 125 26 50 25 25 2 50 6 75 16 00 5 08 6 00 2 inch conduit hole both sides 2 inch conduit hole 6 96 15 00 4 00 5 50 ...

Page 9: ... Be sure to always follow your utility s guidelines and practices when installing equipment When installing the AGI RLC use the following recommended procedures as well as your utility s guidelines and practices 1 Mount the enclosure assembly to the pole using your utility s guidelines and practices 2 If using the optional external antenna attach the antenna cable to its connector within the enclo...

Page 10: ...ch in the manual position there may be damage to the external load or load wiring 4 Using the Set Interrupter Control Relay task in Metercat 3 0 or later can the external load be controlled If Metercat cannot control the load verify that there is no open circuit in the service control extension cable and all its connections If the control cable circuit is functional then replace the meter If Meter...

Page 11: ...February 2012 IL42 4034D 11 Notes ...

Page 12: ...usive or covering all con tingencies If further information is required Elster should be consulted No warranties either expressed or implied including warranties of fitness for a particular purpose or merchantability or warranties arising from the course of dealing or usage of trade are made regarding the information recommendations descriptions warnings and cautions contained herein In no event w...