HighPressure Humidifier - Constant Pressure 

21.1.EN 

15 

 

Elsteam S.r.l - via E.fermi, 496 - 21042 Caronno Pertusella (va) - Tel.+39 02 9659890 - Fax +39 02 96457007 

E-mail: [email protected] - Web: http://www.elsteam.com 

Advanced menu programming fields are: 
 

Display 

Description 

Humidify System 

Enable or disable the humidifier  
 
"Enabled", System on 
"Disabled", System off 

Life Time 

Display the effective working time of the system 
 
This field is read only. Cannot be modified by the user 

Change Oil Timer 

Display the remaining time before pump oil change 
 
This field is read only. Cannot be modified by the user 

Pump Rate 

Set the system flow rate 
 
Indicates the nozzle system flow rate, not the pump one. In the 
current version must be set to minimum value. Will be used to 
provide information about real water consumption.  

Minimum External 

Signal xxx/100% 

Minimum value of external controller signal (only proportional 
controller) 
  
This value is expressed in percentage of 10V. In case of noise on the 
external signal line, parameter value can be increased. (

Default 

value 10%

)  

Output Pressure 

Timeout= xxx sec 

Max time to reach standard pressure in the nozzles network 
 
If within this period from system start, pressure in the nozzles pipe 
has not reached the default value, the embedded controller stops 
the system providing the following error message “Low Output 
Pressure”. 
To restart the system after failure solution, press OK . (

Default value 

60 sec

Minimum On/Off 

Time =   000 sec 

Minimum System On/Off time 
 
To avoid frequent stop and start of the pump (that can damage it) a 
minimum period is set by electronic controller. During this period 
switch on and off of the system is inhibited unless the circuit 
breaker is used (NOT RECOMMENDED). 
In cases of frequent starting and stopping of the pump, increase the 
value. (

Default Value : 60 sec

Std Pressure 

             xxx bar 

Standard value of pressure 
 
This parameter allows the fitter to modify the default value of the 
pressure in the nozzles network. (

Default Value: 80bar) 

4..20mA Coeff. P 

P= xx.xbar)yyyyy 

Pressure transducer Coefficient  
 
On the second line of the LCD display the pressure value and probe 
coefficient are showed. 
(

Default Value: 8850) 

 

 
 
 
 
 
 
 
 
 

To  confirm the changes made  to a  field, use  SET    or    OK.  To  exit the  advanced 
programming mode, press  SET   or   OK. To store the changes in the FLASH memory 
of the microcontroller press  SET   or   OK for more than 3 seconds. Using the  CANC  

key changes to a field will not be stored in FLASH and new values will be valid until 

the next switch off the humidifier (using circuit breaker). 

Summary of Contents for HPN Series

Page 1: ...HPN SERIES HIGH PRESSURE PROPORTIONAL HUMIDIFIER CENTRAL UNITS SOLENOIDS CARDS AND DISTRIBUTION RACK USER INSTALLATION AND MAINTENANCE GUIDE Ver 21 1 EN MAIN UNIT HPNCTRL DISTRIBUTION RACK ...

Page 2: ...NS 3 2 5 WASTE DISPOSAL 4 2 6 WARRANTY 4 3 MANUFACTURER 4 4 WORKING PRINCIPLE 5 5 CHARACTERISTICS 6 6 INSTALLATION PRINCIPLES 7 7 INSTALLATION 8 7 1 MAIN UNIT 8 7 2 HPNCTRL 8 7 3 DISTRIBUTION RACK 8 7 4 DROPLET SEPARATOR 9 7 5 HYDRAULICS CONNECTIONS 9 7 6 ELECTRICAL CONNECTIONS 10 7 7 SETTING OF THE BYPASS CONTROL VALVE 11 8 MAINTENANCE 11 9 ELECTRONIC CONTROLLER 12 9 1 NORMAL OPERATION DISPLAY 12...

Page 3: ... ground connection for the equipment following the safety regulations of the state and at the time when the equipment is installed 2 2 Thermo hygrometric conditions of the installation Check that the environmental conditions of the place where the installation is carried out are always compatible with the requirements of the product as indicated in this manual ELSTEAM products cannot be installed ...

Page 4: ...he disused humidifier to ELSTEAM srl in case of purchase of an equivalent humidifier ELSTEAM will arrange for its own disposal or through its appointees The disposal of electrical or electronic components in an abusive manner and not in compliance with current regulations involves penalties 2 6 Warranty ELSTEAM Srl recognizes on its products the legal guarantees in force at the time of sale of the...

Page 5: ...tant value established based on the model of nozzles used as the number of active network sections varies The HPNCTRL for proportional control of the distribution network is installed in the environment to be humidified or inside the AHU managing section solenoids to make proportional production and feed drain solenoids to activate empty the distribution network One HPNCTRL must be installed for e...

Page 6: ...nlet water quality Supply water shall comply with microbiological requirements of the German Drinking Water Ordinance TrinkwV Supply water must be totally or partially demineralized by drinking water Should the unit be installed using normal water the installer must use a VDI 6022 non return valve to be still compliant Inlet water conductivity μS cm 0 100 Inlet water hardness F 0 5 Input Pressure ...

Page 7: ...ignal of the humidistat 0 10V controls the solenoids controlled card for proportional working mode as well as the activation threshold set at 1V of the high pressure system The following figure shows instead an implementation of an installation with the network of nozzles split in three sections with 33 and 66 thresholds ...

Page 8: ...drain and main unit must be realised respecting local regulation The HPNCRTL card receives the regulation signal ON OFF or Proportional The HPNCRTL unit opens the drain solenoid to empty the solenoids lines when the control signal is 0 7 3 Distribution rack The case of the rack must be installed external to the AHU and fixed using dedicates holes Hydraulic connections to the rack high pressure wat...

Page 9: ... Permanent elastic sealant must be used in such a way to avoid dirt accumulation make surfaces as smooth as possible The droplet separator must be easily removable to perform maintenance operation or unit replacing As the droplet eliminator is not intended to be cleaned it must be replaced at end of its lifetime When installing the droplet separator inside the AHU the holes opened in the panel of ...

Page 10: ...ssage hole and then tighten Connectors for electrical connections are located inside the upper part of the cabinet to access it you need to remove the upper panel of the cabinet It is recommended to isolate the machine from the mains before each intervention and in any case in absence of protective covers dangerously live electrical parts are present inside The power supply line must be connected ...

Page 11: ...tering into the AHU without airflow 7 7 Setting of the bypass control valve The high pressure system has a bypass valve for regulating the output pressure At first power on is necessary to control the adjustment of this valve In the case of a successful installation you can adjust the maximum pressure turning clockwise the valve It is advisable to adjust the output pressure up to a pressure of abo...

Page 12: ...peration the electronic controller display show on the first line main parameters of the system System State u indicates proper operation of the system indicates temperature protection intervention x indicates that no request is present Pump temperature indication bar Minimum operating time of the pump At startup shutdown of the pump t character is displayed During the inhibit time factory setting...

Page 13: ...r to move between fields use and buttons During value changing the value of the field blinks To end the programming of a field press the OK button to set the new value CANC button to cancel modification or OK SET or CANC for more than 3 seconds to exit programming phase Programming phase automatically ends without current parameter update if no button is pressed for 3 seconds Note To save updated ...

Page 14: ...stem the oil counter must be reset by pressing SET and OK buttons When the message Pump Oil has been changed is displayed press OK button to confirm and reset the counter By pressing CANC button the counter is not reset and the system will stop at counter expiration At expiration of extended period the system will stop working and following message will be displayed System Failure Change the Oil o...

Page 15: ... from system start pressure in the nozzles pipe has not reached the default value the embedded controller stops the system providing the following error message Low Output Pressure To restart the system after failure solution press OK Default value 60 sec Minimum On Off Time 000 sec Minimum System On Off time To avoid frequent stop and start of the pump that can damage it a minimum period is set b...

Page 16: ...ent part Message Check Load Valve Driver Cause Driving of input water solenoid failure Possible Solution If W character is displayed in the first line check solenoid connections and voltage 12V Press OK key to remove alarm condition and restart the system If the system is still in alarm please contact ELSTEAM or your distributor for part replacement Message NTC failure Cause The pump temperature p...

Page 17: ...ssure Humidifier Constant Pressure 21 1 EN 17 Elsteam S r l via E fermi 496 21042 Caronno Pertusella va Tel 39 02 9659890 Fax 39 02 96457007 E mail info elsteam it Web http www elsteam com Connections Diagram ...

Reviews: