Display
Description
Provides the option for a time-based or temperature-based defrost cycle.
Considerations
None
Available only with the ems55 series using
OFC
(
Open Front Cooler
) firmware
and the ems75sz.
Range
00 (time-based) or 01 (temperature-based)
Global default
00 (time-based)
9.24
Defrost termination method (dtF)
The table below details the defrost termination method (
dtF
) parameter.
Display
Description
Provides the option to end a defrost cycle as follows:
l
on the defrost duration (
dd
) only
l
on defrost duration (
dd
) or defrost termination temperature
(
dtd
).
If the defrost termination method (
dtF
) is set to use the defrost duration (
dd
)
or the defrost termination temperature (
dtd
), the EMS controller ends the
defrost cycle on the first to occur.
Considerations
Defrost method (
dF
) must be set to 0
Available only with the ems55 series using
OFC
(
Open Front Cooler
) firmware
and the ems75sz.
Range
00 (time[
dd
]) or 01 (time[
dd
] or temperature[
dtd
])
Global default
01 (time or temperature)
9.25
Fan cycle on (FCO)
The table below details the fan cycle on (
FC O
) parameter.
Display
Description
Defines the active period of the evaporator fan while the compressor is
switched off.
Considerations
Fan cycle is the fan cycle on (
FC O
) time + the fan cycle off (
FC F
) time.
Range
1 to 30 minutes
Global default
30 minutes
ems75sz: 5 minutes
9.26
Fan cycle off (FCF)
The table below details the fan cycle off (
FC F
) parameter.