Product Manual, Issue 4
ems100
www.nexo.com
Page 58
5.3.31 Display (dIS)
Display
Description
Defines whether the controller displays the temperature (3.0 for example), or the
word USE during the Ready mode.
Considerations
EMS Controllers will always display alarms regardless of the dIS setting.
Range
00 (USE) or 01 (temperature)
Global default
01 (temperature)
5.3.32 Marketing mode (Ar)
Display
Description
Sets the cooler lights to remain on at all times for display purposes. The coolers lights
will remain on during saving mode.
Considerations
Does not affect saving temperature.
Range
00 (off) or 01 (on)
Global default
00 (off)
5.3.33 Shelf data enable (ShF)
Display
Description
Option to allow the Nexo controller to log stock sensing data to be sent to the cloud.
Considerations
Input will still be operational when viewed via the test routine (tSt).
Stock sensing hardware currently unavailable.
Range
0 (disabled) to 1 (enabled)
Global default
0 (disabled)