SITING THE UNIT
The cylinder must be vertically floor mounted.
Although location is not critical, the following points
should be considered:
The cylinder should be sited to ensure minimum
•
dead leg distances, particularly to the point of
most frequent use.
Avoid siting where extreme cold temperatures
•
will be experienced. All exposed pipe work
should be insulated.
The discharge pipework from the safety valves
•
must have minimum fall of 1:200 from the unit
and terminate in a safe and visible position.
Access to associated controls and immersion
•
heaters must be available to provide for the
servicing and maintenance of the system.
Where these controls are installed against a wall a
minimum distance of 250mm must be left (see
Fig. 1).
Ensure that the floor area for the cylinder is level
•
and capable of permanently supporting the
weight when full of water.
(see Table 1)
WATER SUPPLY
Bear in mind that the mains water supply to the
property will be supplying both the hot and cold
water requirements simultaneously.
It is recommended that the maximum water
demand is assessed and the water supply
checked to ensure this demand can be
satisfactorily met.
Note: A high mains water pressure will not
always guarantee high flow rates.
Wherever possible the mains supply pipe should
be 22mm. We suggest the minimum supply
requirements should be 0.15MPa (1.5 bar) pressure
and 20 litres per minute flowrate. However, at
these values outlet flow rates may be poor if
several outlets are used simultaneously. The higher
the available pressure and flow rate the better the
system performance.
The cylinder has an operating pressure of 0.35MPa
(3.5 bar) which is controlled by the cold water
combination valve assembly. The cold water
combination valve assembly can be connected to a
maximum mains pressure of 1.6MPa (16 bar).
OUTLET/TERMINAL FITTINGS (TAPS, ETC.)
The cylinder can be used with most types of terminal
fittings. It is advantageous in many mixer showers
to have balanced hot and cold water supplies. In
these instances a balanced pressure cold water
connection should be placed between the 2 pieces
of the cold water combination valve assembly (see
Fig. 2). Outlets situated higher than the cylinder will
give outlet pressures lower than that at the heater, a
10m height difference will result in a 0.1MPa (1 bar)
pressure reduction at the outlet. All fittings, pipework
and connections must have a rated pressure of at
least 0.6MPa (6 bar) at 80°C.
GENERAL REQUIREMENTS
Table 1: Unit weights
Fig. 1: Siting the Unit
WALL
Min 250mm
Min 250mm
Type
Model
Reference
Nominal
Capacity
(litres)
Weight of
unit full
(Kg)
Weight
of unit
(Kg)
Indirect
120zi
120
147
27
150zi
150
182
32
170zi
170
204
34
210zi
210
250
40
250zi
250
294
44
300zi
300
352
52
Direct
120zd
120
144
24
150zd
150
178
28
170zd
170
201
31
210zd
210
247
37
250zd
250
289
39
300zd
300
349
49