Parameter setting
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D
• Version: 10.09.2018 • Technical changes and errors excepted.
Switching output
Set the behaviour of the switching output when a threshold value is exceeded/under-
cut. The output switching delay can be set using objects or directly as a parameter.
Block
The switching output can be blocked using an object.
If the block is activated, define specifications here for the behaviour of the output when
blocked.
The behaviour of the switching output on release is dependent on the value of the pa-
rameter "Switching output sends" (see "Switching output")
When the following conditions apply,
the output is
(TV = Threshold value)
• TV above = 1 | TV - hyst. below = 0
• TV above = 0 | TV - hyst. below = 1
• TV below = 1 |TV + hyst. above = 0
• TV below = 0 |TV + hyst. above = 1
Delays can be set via objects
(in seconds)
No • Yes
Switching delay from 0 to 1
(If delay can be set via objects:
valid until first communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching delay from 1 to 0
(If delay can be set via objects:
valid until first communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching output sends
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Cycle
(is only sent if periodically is selected)
5 s • 10 s • 30 s… • 2 h
Use switching output block
No • Yes
Analysis of the blocking object
• At value 1: block | At value 0: release
• At value 0: block | At value 1: release
Blocking object value before first communi-
cation
0 • 1
Behaviour of the switching output
On block
• Do not send message
• send 0
• send 1
On release
(with 2 seconds release delay)
[Dependent on the "Switching output
sends" setting]
Switching output sends on change
• Do not send message
• Send switching output status