Power Supply Systems KNX PS640 and KNX PS640 USB

1

Power Supply Systems KNX PS640 and KNX PS640 USB

 • Version: 19.08.2020 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • 

Technical Service: +49 (0) 7033 / 30945-250

EN

KNX PS640 and KNX PS640 USB

Power Supply Systems

Technical specifications and installation instructions

Item numbers 70140, 70143 (USB)

1.

Description

The 

Power Supply Systems KNX PS640 and KNX PS640 USB

 deliver a 29 V

bus voltage for the KNX system and 24 V DC supply voltage for 24 V devices. Special
operating conditions such as short circuit, overvoltage, overload or excess tempe

-

rature are recorded and may be read off on the display. The present power dischar

-

ge is displayed as well. It is possible to reset the connected bus devices directly by
means of the key pad.

Functions: 

• Delivers a 

29 V KNX bus voltage

 (reduced), output current max. 640 mA, 

short-circuit proof 

• Delivers 

24 V DC

 (not reduced), output current max. 150 mA 

Reset

 of a line directly on the device 

• Record of operating hours, overload, external overvoltage, internal 

overvoltage, short circuit and excess temperature

• Display of operating data bus voltage, bus current and temperature of the 

device

• The display may be shown in German, English, Spanish or Dutch 
• Only 

KNX PS640 USB

: USB interface for bus access via PC

1.1. Deliverables

• Power Supply System

1.2. Technical specifications

The product conforms with the provisions of EU directives.

2.

Installation and Commissioning

2.1. Installation notes

Installation, testing, operational start-up and troubleshooting should 
only be performed by an electrician.

CAUTION!

Live voltage! 

There are unprotected live components inside the device.

• National legal regulations are to be followed.
• Ensure that all lines to be assembled are free of voltage and take

precautions against accidental switching on.

• Do not use the device if it is damaged. 
• Take the device or system out of service and secure it against

unintentional use, if it can be assumed, that risk-free operation is

no longer guaranteed.

The device is only to be used for the intended purpose described in this manual. Any
improper modification or failure to follow the operating instructions voids any and
all warranty and guarantee claims.
After unpacking the device, check it immediately for possible mechanical damage.
If it has been damaged in transport, inform the supplier immediately.

The device may only be used as a fixed-site installation; that means only when as

-

sembled and after conclusion of all installation and operational start-up tasks and
only in the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may
occur after publication of these operating instructions.

2.2. Installation

Observe the correct installation. Incorrect installation may destroy the power supply
system or connected electronic devices.

2.2.1. Housing

2.2.2. Scheme

3.

Operation

3.1. Starting Position

The following may be read off and set on the display of the power supply system
KNX PS640:
• Reset of a line
• Recall of the data memory with operating hours, overcharge, external 

electrical surge, internal electrical surge, short circuit and excess temperature

• Recall of the operating data bus voltage, bus current and temperature
• Language of display
The display is dimmed after 60 seconds if during this period no key is pressed.

3.2. Key functions in display menu

3.3. Line reset

Standard screen: 

Press key   once.

Housing

Plastic

Colour

White

Installation

Snap-on fitting on mounting rails

Degree of protection

IP 20

Dimensions 

approx. 123 x 89 x 61 (W x H x D, mm), 7 
width units

Weight

approx. 370 g

Ambient temperature

Operating 0…+45°C, Storage -25…+70°C

Ambient air humidity

5...95% rH, avoid condensation

Operating voltage

230 V AC, 50 Hz

Power consumption 
Standby

approx. 2.3 W

Outputs

• KNX bus voltage 29 V (reduced),
   Output current max. 640 mA, short-circuit 
proof
• 24 V DC (not reduced), Output current max. 
150 mA

Confirms  the  selection,  moves  to  the  next
step.

One step back.

 

Changes a setting (selects a setting or changes 
a value). The cursor (the blinking rectangle) 
indicates the selected menu item.

ok

Confirms the settings and returns to the device 
main menu.

Fig. 1
1 Bus (KNX te / -)
2 Bus (KNX te / -)
3 Input operating voltage

230 V AC,  L / N / PE

4 USB interface

(only KNX PS640 USB)

5 Output direct current voltage

24 V DC, + / -

Connections 3 and 5 are suitable 
for solid conductors up to 1.5 
mm² or conductors with fine wi

-

res.

3

1

2

4 5

Auxiliary supply 24 V DC

(max. 150 mA)

Fig. 2

0...+45°C

elsner elektronik
KNX Power Supply
Normal Operation
Diagnostics >

elsner elektronik
KNX Power Supply
Normal Operation
Diagnostics >

Line Reset 

>  ™

Data Memory

>

Operating Data >
Language

>