24
Parameter setting
Temperature evaluation unit KNX T6-UN-B4
• Version: 17/12/2019 • Technical changes and errors excepted.
5.
Parameter setting
5.1.
Behaviour on power failure/ restoration of
power
Behaviour following a failure of the bus power supply:
The device sends nothing.
Behaviour on bus restoration of power and following programming or reset:
The device sends all outputs according to their send behaviour set in the parameters
with the delays established in the "General settings" parameter block. The "Software
version" communications object is sent once after 5 seconds.
5.2.
General settings
Set basic characteristics of data transfer.
5.3.
Temperature measured values
Activate the measured values that you want to use here. The
Temperature evalua-
tion unit KNX T6-UN-B4
provides six measured values for temperature.
5.3.1. Measured value 1...6
Choose whether a
Malfunction object
should be transmitted.
Use
Offsets
to adjust the readings to be sent.
Send delay after reset and programming for:
Measured values, threshold values, switch-
ing output
5 s • ... • 2 h
Temperature controller outputs
5 s • 10 s • ... • 2 h
Switch interfaces and logic
5 s • 10 s • ... • 2 h
Maximum telegram rate
• 1 message per second
• ...
• 10 messages per second
• ...
• 20 messages per second
Use measured values 1/2/3/4/5/6
Yes • No
Use malfunction object
Yes • No
Offset in 0.1°C
-50…50; 0