Installation and start-up

Brightness and Wind Sensor KNX LW sl

 • Status: 05.11.2014 • Errors excepted. Subject to technical changes.

The product is compliant with the provisions of EC guidelines:

EMC Directive 2004/108/EC

The following standards and/or technical specifications were applied:

EN 50491-5-1: 2010

EN 50491-5-2: 2011

EN 60730-1: 2011

2.

Installation and start-up

2.1. Installation notes

Installation, testing, operational start-up and troubleshooting should 
only be performed by an electrician.

Auxiliary supply

12…40 V DC, 12…28 V AC.
An appropriate power supply unit can be purchased 
from Elsner Elektronik.

Auxiliary current

at 12V DC: max. 185 mA
at 24V DC: max. 90 mA
at 24V AC: max. 82 mA

Bus current

max. 10 mA

Data output

KNX +/-

BCU type

Integrated microcontroller

PEI type

0

Group addresses

max. 2000

Assignments

max. 2000

Communication objects

303

Wind sensor:

Measurement range

0 m/s … 35 m/s

Resolution

0.1 m/s

Accuracy

±15% of the measurement value when incoming flow 
is 45°…315°
(Frontal incoming flow corresponds to 180°)

Brightness sensor:

Measurement range

0 lux … 150,000 lux

Resolution

    1 lux at 0…255 lux
    4 lux at 256…2,645 lux
163 lux at 2,646…128,256 lux
762 lux at 128,257…150,000 lux

Accuracy

±15% of the measurement value at 35 lux … 150,000 
lux

Summary of Contents for 70164

Page 1: ...em number 70164 EN Elsner Elektronik GmbH Control and Automation Engineering Sohlengrund 16 D 75395 Ostelsheim Phone 49 0 70 33 30 945 0 info elsner elektronik de Germany Fax 49 0 70 33 30 945 20 www...

Page 2: ...computed values Threshold values can be adjusted per parameter or via communication objects 8 AND and 8 OR logic gates each with 4 inputs All switching events as well as 16 logic inputs in the form o...

Page 3: ...DC 12 28 V AC An appropriate power supply unit can be purchased from Elsner Elektronik Auxiliary current at 12V DC max 185 mA at 24V DC max 90 mA at 24V AC max 82 mA Bus current max 10 mA Data output...

Page 4: ...only be used as a fixed site installation that means only when assem bled and after conclusion of all installation and operational start up tasks and only in the surroundings designated for it Elsner...

Page 5: ...s excepted Subject to technical changes Fig 2 The device must be attached to a vertical wall or a pole wall or pole 90 Fig 3 The device must be mounted in the horizontal transverse direction Horizonta...

Page 6: ...amage the device electronics Do not open the device if water e g rain can get into it Fig 5 1 Programming LED 2 Brightness measurement 3 Wind measurement 4 Programming key on the underside of the hous...

Page 7: ...wall or pole installation Wall installation Use fixing materials dowels screws that are suitable for the base Fig 6 Slacken both screws on the lid top and low er part bottom with a size 6 Torx screwdr...

Page 8: ...drilling plan is included ex works and this can be used as a tem plate Fig 9 a b a If the power lead is to be hidden when in stalled it must emerge from the wall in the vicinity of the rear of the ho...

Page 9: ...2 4 3 Connection The connector is in the lower part of the housing Fig 11 Dimensions in mm Variations are possible for technical reasons A B2 longitudinal holes 8 mm 5 5 mm C Position of the cable ou...

Page 10: ...measurement value and thus also all wind switching outputs cannot be out put until 35 seconds after the power is turned on Fig 14 Connect KNX data and power supply 12 40V DC 12 28V AC 1 2 to the conne...

Page 11: ...s 3 Addressing the equipment The equipment is delivered ex works with the bus address 15 15 250 You program a different address in the ETS by overwriting the address 15 15 250 or teach the device usin...

Page 12: ...d place people in danger e g moving windows awnings if a rain wind alarm has been triggered while cleaning Always isolate the device from the mains for servicing and cleaning The device must regularly...

Reviews: