Safety and operating instructions

Weather Station P04/3-RS485

 • Version: 09.06.2022 • Errors excepted. Subject to technical changes.

1.

Safety and operating instructions

Installation, testing, operational start-up and troubleshooting should 
only be performed by an authorised electrician.

CAUTION!
Live voltage! 

There are unprotected live components inside the device.

• Inspect the device for damage before installation. Only put undamaged 
devices into operation. 
• Comply with the locally applicable directives, regulations and provisions for 
electrical installation. 
• Immediately take the device or system out of service and secure it against 
unintentional switch-on if risk-free operation is no longer guaranteed.

Use the device exclusively for building automation and observe the operating instruc-
tions. Improper use, modifications to the device or failure to observe the operating in-
structions will invalidate any warranty or guarantee claims.
Operate the device only as a fixed-site installation, i.e. only in assembled condition and
after conclusion of all installation and operational start-up tasks, and only in the sur-
roundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may occur
after publication of these operating instructions.

For information on installation, maintenance, disposal, scope of 
delivery and technical data, please refer to the installation 
instructions.

2.

Description

The 

Weather Station P04/3-RS485

 measures temperature, wind speed, brightness

and it recognizes precipitation. 

The weather station sends the currently recorded weather data, date and time once
every second. This data can be analyzed by an end device such as SPS, PC or MC. The

P04/3-RS485

 has 2 connections for data output (A/B) and 2 for power supply (24 V

DC).

Functions:

Brightness measurement

 with 3 separate sensors for east, south and west. 

Recognition of twilight/dawn

Wind measurement:

 The wind strength measurement takes place 

electronically and thus noiselessly and reliably, even during hail, snow and 
sub-zero temperatures. Even turbulent air and anabatic winds in the vicinity of 
the weather station are recorded

Summary of Contents for 30152

Page 1: ...P04 3 RS485 Weather Stations Item numbers 30152 P04 3 RS485 GPS 30153 P04 3 RS485 CET 30154 P04 3 RS485 basic Installation and Adjustment EN ...

Page 2: ......

Page 3: ...r Station P04 3 RS485 Status 09 06 2022 Errors excepted Subject to technical changes 1 Safety and operating instructions 3 2 Description 3 3 Notes on commissioning 4 4 Transfer protocol 4 4 1 Protocol P04 3 RS485 GPS 4 4 2 Protocol P04 3 RS485 CET 6 4 3 Protocol P04 3 RS485 basic 7 ...

Page 4: ...s available Clarification of signs used in this manual Safety advice Safety advice for working on electrical connections components etc DANGER indicates an immediately hazardous situation which will lead to death or severe injuries if it is not avoided WARNING indicates a potentially hazardous situation which may lead to death or severe injuries if it is not avoided CAUTION indicates a potentially...

Page 5: ... site installation i e only in assembled condition and after conclusion of all installation and operational start up tasks and only in the sur roundings designated for it Elsner Elektronik is not liable for any changes in norms and standards which may occur after publication of these operating instructions For information on installation maintenance disposal scope of delivery and technical data pl...

Page 6: ...voltage has been connected 4 Transfer protocol All characters and or digits are based on the ASCII standard i e every reading pro cessed internally as an integer or float value will always be broken down into and trans ferred in its individual ASCII format characters They must then be reassembled in the reverse process by the receiver Transfer rate 19200 Baud Data bits 8 Stop bit 1 Parity none The...

Page 7: ...3 0 9 UTC date day tens digit 24 0 9 UTC date day units digit 25 0 9 UTC date month tens digit 26 0 9 UTC date month units digit 27 0 9 UTC date year tens digit 28 0 9 UTC date year units digit 29 0 9 UTC time hour tens digit 30 0 9 UTC time hour units digit 31 0 9 UTC time minute tens digit 32 0 9 UTC time minute units digit 33 0 9 UTC time second tens digit 34 0 9 UTC time second units digit 35 ...

Page 8: ...o Char Description 1 W Start of string 2 Outdoor temperature in C sign 3 0 9 Outdoor temperature in C tens digit 4 0 9 Outdoor temperature in C units digit 5 Outdoor temperature in C decimal point 6 0 9 Outdoor temperature in C tenths digit 7 0 9 Sun south in kLux tens digit 8 0 9 Sun south in kLux units digit 9 0 9 Sun west in kLux tens digit 10 0 9 Sun west in kLux units digit 11 0 9 Sun east in...

Page 9: ... thousands digit 37 0 9 Checksum hundreds digit 38 0 9 Checksum tens digit 39 0 9 Checksum units digit 40 0x03 end identifier Byte No Char Description 1 W Start of string 2 Outdoor temperature in C sign 3 0 9 Outdoor temperature in C tens digit 4 0 9 Outdoor temperature in C units digit 5 Outdoor temperature in C decimal point 6 0 9 Outdoor temperature in C tenths digit 7 0 9 Sun south in kLux ten...

Page 10: ...ed Subject to technical changes 19 Wind in m s decimal point 20 0 9 Wind in m s tenths digit 21 J N Rain indication 22 0 9 Checksum thousands digit 23 0 9 Checksum hundreds digit 24 0 9 Checksum tens digit 25 0 9 Checksum units digit 26 0x03 end identifier Byte No Char Description ...

Page 11: ......

Page 12: ...e You can reach the technical service of Elsner Elektronik under Tel 49 0 70 33 30 945 250 or service elsner elektronik de We need the following information to process your service request Type of appliance model name or item number Description of the problem Serial number or software version Source of supply dealer installer who bought the device from Elsner Elektronik Questions about the product...

Reviews: