Fig. 6.4
Navigation is performed by sending number to terminal. User then proceeds by following further on-screen
instructions. For example, to set Baudrate, press [2] to enter Baudrate screen; press [1] to edit; enter new
configuration; press [RETURN] to save, or [ESC] to cancel changes. When done, press [0] (exit) before disconnecting
device. Default values is set by pressing [7] on main screen, and confirming changes [1]. If accidentally closed the
terminal window, user can connect terminal program again, and press any key on keyboard to show up main menu.
c. Main Menu
Main Menu
Function
Values
Default Values
1.
Slave Address
Modbus Slave address / ID
1-247
(default: 1)
2.
Modbus Baudrate
Modbus Baudrate
100 - 256000
(default: 9600)
3
3.
Data, Stop and Parity bits
Chooses Stop and parity
bits to use
(default: 8N1)
4
4.
RS485 Terminating
Resistor
RS485 120 Ohms
Terminating Resistor
0 - 1 (off/on)
(default: 0)
5.
Relay #1 settings
Active mode and active
range
Active mode: 1 –Relay
disabled; 2- Temperature
active 3- Humidity active;
active range: -10 to 60
(temperature) and 0 to 100
(humidity)
(default: 0)
6.
Relay #2 settings
Active mode and active
range
Active mode: 1 –Relay
disabled; 2- Temperature
active 3- Humidity active;
active range: -10 to 60
(temperature) and 0 to 100
(humidity)
(default: 0)
7.
Set Default Settings
Sets Default Settings
(1 to confirm, 0 to cancel)
-
8.
Firmware Upgrade
Mass Storage Device
Firmware Upgrade
(1 to confirm, 0 to cancel)
-
0.
Exit
Exit and disconnect
-
-
d. Firmware upgrade over USB
To update device firmware user must enter main configuration menu.
Enter Firmware update screen by pressing [4];
Confirm update by pressing [1];
Device now enters Firmware Upgrade mode.