ELREHA TAR 1370 Manual Download Page 2

page 2

Technical Manual TAR Cold Storage Controller TAR 1370

Param. Code Description

Range

Default

Your value

No.

onl.

P01

Actual temperature control sensor  (°C or °F)

display only

P02

Actual temperature evaporator sensor (°C or °F)

display only

P03

no

Setpoint

Low limit P08...high limit P07

0 °C

P07

88

Highest adjustable setpoint

± 100 °C (-148...212 °F)

+50 °C

P08

88

Lowest adjustable setpoint

-100°C / -148°F up to (P07)

-50°C

P09

88

Setpoint hysteresis

0,3...20,0 K

2 K

P10

88

Switching mode cool. (compressor) relay

1= refrigeration, 2= heating

1 (refrig.)

P11

88

Cooling relay idle time

0...59 minutes

2 minutes

P12

88

Fan operation threshold

-100°C... +100°C (hyst. 3K fixed)

50°C

P13

88

Fan operating mode

1=, 2=, 3=, see text

1

P14

88

Fan delay after defrost

0...30 minutes

3 minutes

P15

Remaining minutes till defrost ends

display only

P16

Remaining minutes to activate cooling

display only

P17

Remaining minutes to start fan relay

display only

P18

Remaining minutes up to an alarm

display only

P19

88

Calibration control sensor

+/-10,0 K/F

0 K

P20

88

Calibration evap. sensor, resp. sensor OFF

+/-10,0 K/F, oFF

0 K

P21

70

Sensor type / °C or °F / measuring range

1= TF 501 / °C / -110...+120°C

2

2= TF 201 / °C / -55...+105°C

3= TF 501 / °F / -166...248°F

4= TF 201 / °F / -67...221°F

5= TF 202 / °C / -55...+105°C

6= TF 202 / °F / -67...221°F

P22

88

Defrost termination temperature in °C or °F

0,0...30,0°C / 118,0°F

10°C

P23

88

Defrost type

1= heater defrost by cyclic timer

1

2= hot gas defrost by cyclic timer

3 = heater defr. by cooling runtime.

4 = hot gas defrost by cooling runtm.

P24

88

Defrost cycle

1...99 hours

4 hours

P28

88

Defrost duration

0...120 minutes

30 min.

P29

88

Drain time  (refrigeration delay after defrost)

0...99 minutes

0 min.

P30

88

Alarm mode

0= Alarm relay active ON (N / O)

1= Alarm relay active OFF (N / C)

2= no function

3= no function

4= Alarm relay resettable (see text)

1

P31

88

Alarm delay

1...99 minutes (if sensor fails always

< 1 flashing display)

5 minutes

P32

88

Alarm high limit temperature (relative to P03)

0...100 K

100K

P33

88

Alarm low limit (absolute value)

± 100 °C

-100°C

P37

no

Manual defrost

"

!

"= Start defrost event

"

"

"= Terminate defrost event

P38

no

Access Code

0...99

0

Please note that you need a different code for
changing sensor type.

Default values are factory set values.

Summary of Contents for TAR 1370

Page 1: ... Controller with cyclic defrost Manual No 5311009 05 04 E Software Version 011118 TAR 1370 TAR 1370 H Start up Troubleshooting information you will find on pages 4 5 TAR increase values decrease values refrig ON defrost ON P ELREHA alarm fan ON Program ming enter Technical Data Supply Voltage 12V AC DC 11 18V DC Power Consumption appr 3 VA Contact Rating Cooling Relay 10 A peak 80 A 10 msec other ...

Page 2: ...ensor 10 0 K F 0 K P20 88 Calibration evap sensor resp sensor OFF 10 0 K F oFF 0 K P21 70 Sensor type C or F measuring range 1 TF 501 C 110 120 C 2 2 TF 201 C 55 105 C 3 TF 501 F 166 248 F 4 TF 201 F 67 221 F 5 TF 202 C 55 105 C 6 TF 202 F 67 221 F P22 88 Defrost termination temperature in C or F 0 0 30 0 C 118 0 F 10 C P23 88 Defrost type 1 heater defrost by cyclic timer 1 2 hot gas defrost by cy...

Page 3: ...rflow Defrost by cyclic timer Starting of defrost event switches ON defrost relay i e heater ON and switches OFF the cooling 2 Hot Gas Defrost by cyclic timer Starting of defrost event switches ON defrost relay i e bypass valve open and switches ON cooling relay i e solenoid valve open 3 Heater or Airflow Defrost by cooling runtime Starting a defrost event switches ON defrost relay i e heater ON a...

Page 4: ...onal injury or damage to property caused by inadequate handling or non observance of the safety instructions The guarantee will lapse in such cases If you notice any damage the product may not be connected to mains voltage Danger of Life A riskless operation is impossible if The device has visible damages The device doesn t work After a long time storage under unfavorable conditions After inadequa...

Page 5: ... appr F selected Wiring or sensor itself broken Sensor type TF 501 with C appr F selected Wiring or sensor itself broken Check if reference thermometer is placed at the same position as the sensor head Then correct sensors High and low limit of the setpoint range are identical Enter Access Code Unitworksinselftestmode SwitchpowerOFF switchpowerOnagainafter15 seconds Please check sensor corrections...

Page 6: ...his statement is made from the manufacturer importer by ELREHA Elektronische Regelungen GmbH Klaus Birkner Developement and 68766 Hockenheim and leader of the EMC Laboratory Name Anschrift name adress Hockenheim 23 3 2000 Ort city Datum date Unterschrift sign Dimensions Wiring Front frame can be removed Snap in fixing frame from rear side 1 2 3 4 35 1 38 76 3 0 TAR P ELREHA 75 2 95 Rückansicht mit...