ELREHA TAR 1370 Manual Download Page 1

Parameters

All selectable parameters hold a parameter number (e.g. P03), you
will find a listing on the next page.

Calling up and editing

Press key 'P' ............ parameter number appears
Use '

!

/

"

' ................. select desired parameter

Press "P" again ........ parameter value appears
Use keys '

!

/

"

' ......... adjust parameter value

Press 'P' again ......... value is stored, back to parameter no.

Unlock Keys

To prevent un-authorized persons from editing parameter values, there is
a locking function which allows only the most important parameters to be
changed at any time. All other parameters must be unlocked beforehand.

Press key "P" ............. parameter number appears
Use "

!

/

"

" ................. select code parameter (P38)

Press "P" again .......... parameter value appears
Use "

!

" ..................... set value to --88--

Press "P" again .......... value is stored, back to parameter no.

If no key is hit for about four minutes, the access code is cancelled and
the editing function is locked automatically.

Auto scrolling

Hold '

!

/

"

'-keys to scroll values automatically.

Manual Defrost

Manual defrost can be initiated out of programming mode by depressing
'

!

' for more than 2 seconds - to terminate: press '

"

' for more than 2

seconds.

Reading the controller type

Hold key 'P' for more than 2 seconds, the display shows the type of
the controller unit (

137

).

Set parameters to factory default

- Switch off supply voltage, press and hold the 'P'-key
- switch on supply voltage
- hold the key for about 5 more seconds
While holding the key, the display shows one by one: software-
version, date and 'def.'. 'def' signifies that all parameters are set to
default values now.

Reset internal Beeper 

(TAR 1370 H only)

The internal beeper can be reset by any keypress.

ELEKTRONISCHE REGELUNGEN GMBH

Product Description

Cold Storage Controller with 4 relays for Solenoid Valve, Defrost
heater, Fan and Alarm Forwarding. Usable for any kind of cold
storages such as walk-in coolers/freezers, refrigerated shelfs,
refrigerated counters, etc..

Operating Elements

Cold Storage Controller
with cyclic defrost

Manual No.

5311009-05/04 E

Software Version

011118

TAR 1370
TAR 1370 H

Start-up / Troubleshooting

 information you will find

on pages 4 + 5.

TAR

increase 
values

decrease
values

refrig. ON

defrost ON

P

ELREHA

alarm

fan ON

Program-
ming /
enter

Technical Data

Supply Voltage .....................................

12V AC/DC (11-18V DC)

Power Consumption .................................................... appr. 3 VA
Contact Rating Cooling Relay .......... 10 A (peak 80 A / 10 msec)

other relays .......... 8A cos phi = 1, 3A ind. / 250V

The current over terminal 7 may not increase 12 A !

Operating temperature ............................ -10...+55°C (14...131°F)
Storage temperature .............................. -30...+70°C (-22...158°F)
Relative Humidity ......................... max. 80% r.H., not condensing
Display ........... LED, 7-segment, red, character height 13mm (.51)
Resolution ................................................................ 0,1°C / 0,2°F
Accuracy ...................................................................... typ. +/- 1K
Temperature sensors ............ TF 201, TF 202 or TF 501 (Pt1000)
Control-/Display Range

with TF 201/202 ........................ -55...+105°C / -67...221°F
with TF 501 .......................... -110...+120°C / -166...248°F

Data storage parameters ......................................... typ. unlimited
Relay indicators ........................................................... 3 mm, red
Beeper (TAR 1370 H only) ..................................... 2x per second
Electrical connection ............................... screw terminals 2,5mm²
Protection ............................................................ IP 54 from front

Accessories 

(please order separately)

Temperature sensors ................................. 2x TF 201 or TF 501
Transformer .......................... 107-1300-0052 (230V/ 12V / 5VA)

Please read this manual carefully before using the product. The guarantee will lapse in case
of damage caused by failure to comply with these operating instructions! We shall not be liable
for any consequent loss! We do not accept liability for personal injury or damage to property
caused by inadequate handling or non-observance of the safety instructions! The guarantee
will lapse in such cases. This manual, which is part of the product, has been set up with care
and our best knowledge, but mistakes may occur. Technical details can be changed without
notice, especially the software. Please note that the described functions are only valid for units
containing the software version-number shown on page 1.

ELREHA Gmbh

D-68766 Hockenheim, Germany, 

Schwetzinger Str. 103

phone 0 62 05 / 2009-0  -  fax 0 62 05 / 2009-39  -  [email protected]

Please Note Safety Instructions !
Please note supply voltage when
replacing older types !

Summary of Contents for TAR 1370

Page 1: ... Controller with cyclic defrost Manual No 5311009 05 04 E Software Version 011118 TAR 1370 TAR 1370 H Start up Troubleshooting information you will find on pages 4 5 TAR increase values decrease values refrig ON defrost ON P ELREHA alarm fan ON Program ming enter Technical Data Supply Voltage 12V AC DC 11 18V DC Power Consumption appr 3 VA Contact Rating Cooling Relay 10 A peak 80 A 10 msec other ...

Page 2: ...ensor 10 0 K F 0 K P20 88 Calibration evap sensor resp sensor OFF 10 0 K F oFF 0 K P21 70 Sensor type C or F measuring range 1 TF 501 C 110 120 C 2 2 TF 201 C 55 105 C 3 TF 501 F 166 248 F 4 TF 201 F 67 221 F 5 TF 202 C 55 105 C 6 TF 202 F 67 221 F P22 88 Defrost termination temperature in C or F 0 0 30 0 C 118 0 F 10 C P23 88 Defrost type 1 heater defrost by cyclic timer 1 2 hot gas defrost by cy...

Page 3: ...rflow Defrost by cyclic timer Starting of defrost event switches ON defrost relay i e heater ON and switches OFF the cooling 2 Hot Gas Defrost by cyclic timer Starting of defrost event switches ON defrost relay i e bypass valve open and switches ON cooling relay i e solenoid valve open 3 Heater or Airflow Defrost by cooling runtime Starting a defrost event switches ON defrost relay i e heater ON a...

Page 4: ...onal injury or damage to property caused by inadequate handling or non observance of the safety instructions The guarantee will lapse in such cases If you notice any damage the product may not be connected to mains voltage Danger of Life A riskless operation is impossible if The device has visible damages The device doesn t work After a long time storage under unfavorable conditions After inadequa...

Page 5: ... appr F selected Wiring or sensor itself broken Sensor type TF 501 with C appr F selected Wiring or sensor itself broken Check if reference thermometer is placed at the same position as the sensor head Then correct sensors High and low limit of the setpoint range are identical Enter Access Code Unitworksinselftestmode SwitchpowerOFF switchpowerOnagainafter15 seconds Please check sensor corrections...

Page 6: ...his statement is made from the manufacturer importer by ELREHA Elektronische Regelungen GmbH Klaus Birkner Developement and 68766 Hockenheim and leader of the EMC Laboratory Name Anschrift name adress Hockenheim 23 3 2000 Ort city Datum date Unterschrift sign Dimensions Wiring Front frame can be removed Snap in fixing frame from rear side 1 2 3 4 35 1 38 76 3 0 TAR P ELREHA 75 2 95 Rückansicht mit...

Reviews: