COLINEAR
ANTENNA
MAST
OPTIONAL
PADLOCK
SURGE
ARRESTOR
(OPTIONAL)
COAXIAL CABLE
WEATHERPROOF
CONNECTORS WITH
“3M 23” TAPE
STRESS RELIEF
LOOP
PROVIDE GOOD GROUND
CONNECTION TO MAST, MODULE
AND SURGE ARRESTOR
CHASSIS
GND
IF GROUND CONDITIONS ARE
POOR, INSTALL MORE THAN
ONE STAKE
1 wavelength
minimum
Wireless I/O
905U-K-
IP
SOLAR PANEL
(See Notes)
Antenna Installation
Wavelength Guide
150MHz = 150cm
340MHz = 88cm
450MHz = 66cm
900MHz = 33cm
905U-K-IP Wireless Solar-Battery Enclosure
Installation Guide
Installation and Configuration
The ELPRO 905U-K is configured using the E-Series Configuration tool. Please down load the
configuration tool from the ELPRO web site:
Configuration is performed by using the ELPRO E-Series configuration PC tool and connecting
connecting to the RS-232 connector
Please download the configuration tool for the 905U-K module from the ELPRO website:
https://elpro.com.au/wp-content/uploads/2018/06/BUS_WIR_Inst_EConfig.2.1.0.412.zip
For further information on installation and configuration please refer to the 905U-K user manual that can
be found at the ELPRO web page:
https://elpro.com.au/wp-content/uploads/2018/06/bus-wir-man-905K-1.10.pdf
Battery Power Applications:
Units shipped with internal battery option do not have the battery connected during
shipping.
CAUTION - Lithium Primary (LiP non-rechargeable) internal battery:
DO NOT
connect external voltage directly to battery terminals or to supply/solar terminals as
this battery is
NOT rechargeable
and damage may result.
CAUTION - Lithium Iron Phosphate (LFP rechargeable):
DO NOT connect
external voltage directly to battery terminals as this may result in damage or
overheating of battery pack.
To connect the internal battery:
·
Remove the battery holder by removing the two Philips screws and battery
bracket.
·
Locate the battery connector located at the top
right of battery as shown in picture.
·
For internal battery connect the battery by
plugging battery cable connector onto the two
pin connector on circuit board located to right
of internal/external selection link, using correct
orientation (keyed).
·
The PWR/OK LED green flash every 10 seconds in normal operation. See unit
configuration on reverse side of this document.
©
ELPRO Technologies Pty. Ltd.
2020 Rev. 1.0
905U-K
1
2
3
4
5
6
7
8
9
G
N
D
L
O
O
P
S
U
P
V
B
A
T
S
O
L
A
R
ꟷ
S
O
L
A
R
+
G
N
D
A
IN
+
S
U
P
P
L
Y
D
IG
IT
A
L
A
N
A
L
O
G
Vdc
mA
A
IN
ꟷ
G
N
D
D
IO
1
D
IO
2
D
IO
3
D
IO
4
G
N
D
SUPPLY:
Ꝋ SOLARꟷ :
Solar Panel or supply negative,
Internally connected to GND
Ꝋ SOLAR+:
Solar Panel Positive 10W MIN 2A
Max or Ext Supply 17-30Vdc
Ꝋ GND:
Battery or External Power -ve supply
Ꝋ VBAT:
External Power 11-15Vdc
POWER/OK LED
RADIO TX LED
DIGITALS:
Ꝋ GND:
Ꝋ DIO1:
ON/OFF, Pulse
Ꝋ DIO2:
ON/OFF, Pulse
Ꝋ DIO3:
ON/OFF only
Ꝋ DIO4:
ON/OFF only
Ꝋ GND:
ANALOG INPUT:
Ꝋ GND:
Ꝋ AIN1 -/+:
4-20mA Current Loop or 0-10Vdc
Ꝋ AIN2 -/+:
4-20mA Current Loop or 0-10Vdc
Ꝋ LOOP:
+24V Loop Or sensor Supply
RS232:
Configuration port
Analog Input:
Select 4-20mA or 0-10Vdc
CONNECTIONS:
Wiring Entry:
IP66 M20 Cable entry Gland (5-13mm)
Terminals:
PushIN connection max 0.2
– 1.5mm
2
wire.
905U-K-IP
Weatherproo
f
Wireless I/O
WARNING: DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS
KNOWN TO BE NON-HAZARDOUS
Battery
Connection