A, B: Connect RS485

(Modbus)

RS485 

termination

switch

Up = terminated

Down = un-terminated

Power and

Modbus

connector 

Modbus 

Master

115S

115S

115S

A

A

B

A

B

A

B

RS485

RS485 

Termination 

switch up 

(terminated)

Set a unique Modbus slave address for each 115S 
connected to the Modbus Master 
Example shows address “01”
Consult user manual for Modbus addresses

ADDRESSING

x10

x1

115S

B A  

- +

POWER

Modbus 

Master

Power 

Supply

Power Connections:

EARTH wiring minimum  2mm² - 14 AWG 

B  A  

- +

ON

115S Quick Setup Guide - Connections

inst_115S_1.13.vsd

© 

ELPRO Technologies.

Address switches must be 00 for E-Series protocol
Example shows address “00”
Setup using ELPRO E-Series configuration utility.

ADDRESSING

x10

x1

Connection to Modbus Master

Connection to E-Series Radio

Power

Power

Power

Modbus

Modbus

Modbus

+

-

A, B: Connect RS485

(Elpro)

RS485 

Termination

switch

Up = terminated

Down = un-terminated

Power and

RS485 

connector 

E-Series 

Module

115S

115S

115S

A

B

A

B

A

B

A

B

RS485

RS485 

Termination 

switch up 

(terminated)

B A  

- +

POWER

E-Series 

Radio

Power 

Supply

Power Connections:

115S-11: 300mA max
115S-12: 900mA max
115S-13: 900mA max

+

-

B  A  

- +

RS485 

Termination 

switch up 

(terminated)

ON

**Check rear label for 

operating voltages

Power

Power

Power

RS485

RS485

RS485

Battery

_

+

Supply

Earth

115S

115S

B

RS485 Termination 

switch up (terminated)

or 

120

 Fitted across 

RS485

115S

115S

115S

Earth

Earth

Earth

Earth

Earth

Earth

Earth

Earth

Earth

‘+’ : Pos Supply 

(10.8 to 30 VDC**)

‘-’ : Neg Supply

Ensure all earth connections are at the same potential.

EARTH wiring minimum 2mm² - 14 AWG 

Ensure all earth connections are at the same potential.

THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS 1 DIVISION 2 GROUPS A,B,C AND D, OR NONHAZARDOUS LOCATIONS ONLY.

WARNING

EXPLOSION HAZARD 

DO NOT DISCONNECT EQUIPMENT WHILE THE CIRCUIT IS LIVE OR UNLESS THE AREA IS KNOW TO BE FREE OF IGNITABLE CONCENTRATIONS.

WARNING

EXPLOSION HAZARD 

SUBSTITUTION OF ANY COMPONENT MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2.

115S-11: 300mA max
115S-12: 900mA max
115S-13: 900mA max

**Check rear label for 

operating voltages

‘+’ : Pos Supply 

(10.8 to 30 VDC**)

‘-’ : Neg Supply