XIII.  Parameter Level, 

individual selectable for zones 1...4 

 

Select zone “n” and press „P“ - and „E“ - key appr. 1 sec. 

 
Display 

Parameter 

Display  

"Process" 

 

„Set“ 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 

valid output ratio   

-100...0...100 % 

The output ratio shows the momentary calculated ratio. 

 

 

 

 

 

 

It cannot be altered. The display is in percent of the installed 

 

 

 

 

 

 

performance capability for heating or cooling. 

 

 

 

 

 

 

Output ratio for cooling is shown as a negative value. 

   
 
1Y.Hi 

output ratio limit   

0...100 %  

 

 

(ex works: 100) 

 

„heating“ 

 

 

 

Limitation of the output ratio is only necessary when: 

 

 

 

 

 

 

the heating or cooling energy supply is grossly over- 

 

 

 

 

 

 

dimensioned compared to the power required, or 

 

 

 

 

 

 

to turn off a control output (setting = 0%).  

 

 

 

 

 

 

 

 

under normal circumstances no limitation is needed (setting = 0%). 

 

 

 

 

 

 

the limitation becomes effective, when the controllers’ calculated 

 

 

 

 

 

 

output ratio is greater than the maximum permissible (limited) ratio. 

 

 

 

 

 

 

Warning! 

 

 

 

 

 

 

The output ratio limitation does not work during autotune. 

 

 

 

 

 

 

 
2Y.Hi 

output ratio limit   

0...100 %  

 

 

(ex works: 100) 

 

„cooling“ 

 

 

 

 

 
 
1  P 

„heating“ 

 

OFF; 0,1...100,0 %  

 

(ex works: 3,0) 

 

prop. band (P) 

 

 

 

If „ 1 P “  = OFF (control action: on-off, without feedback) 

 

 

 

 

 

 

next parameter: „ 1 Sd “.  

 
 
1  d  

„heating“  

  

OFF; 1...200 secs   

 

(ex works: 30) 

 

rate (D) 

 
1  J 

„heating“  

 

OFF; 1...1000 secs  

 

(ex works: 150) 

 

reset (I)   

 

 

 

Normally the controller works using PD/I control action. 

 

 

 

 

 

 

This means, controlling without deviation and with practically  

 

 

 

 

 

 

no overshoot during start-up. 

 

 

 

 

 

 

The control action can be altered in its structure by making the 

 

 

 

 

 

 

following adjustments to the parameters: 

 

 

 

 

 

 

a. no control action, on-off  (setting P = OFF) 

 

 

 

 

 

 

b. P-action  

(setting D and I  = 0) 

 

 

 

 

 

 

c. PD-action  

(setting           I  = 0) 

 

 

 

 

 

 

d. PI-action  

(setting           D = 0) 

 

 

 

 

 

 

e. PD/I    

modified PID-action 

 
1  C 

„heating“ 

 

0,5...240,0 secs 

 

 

(ex works: 10,0) 

 

cycle time 

 

 

 

The switching frequency of the actuator can be determined 

 

 

 

 

 

 

by adjusting the cycle time. This is the total time needed for the 

 

 

 

 

 

 

controller to switch on and off once. 

 

 

 

 

 

 

a) 

Relay outputs: 

 

cycle time > 10 secs 

 

 

 

 

 

 

b) 

Bistable voltage outputs:  

cycle time 0,5...10 secs 

 
1  Sd  

„heating“ 

 

Control sensitivity  

Only if:  1  P  =  Xp  =  OFF  (On-off action, without feedback) 

 

 

 

 

OFF; 0,1...80,0     °C 

(ex works: 0,1) 

 

 

 

 

OFF; 0,01 ... 8,00 °C    (ranges with dec.point ) 

 
 

 

 

 

 

 

 

    Sd = 10,0 

 
 
 

 

 

 

 

 

on 

 
 
 

 

 

 

 

 

              -5,0 

   +5,0 

 

off 

 
 
 
 
 

 

 

 

 

 

 

   SETPOINT 

   PROCESS VALUE 

 
 

Summary of Contents for R 2000 - 431

Page 1: ...ontroller Heater Current Monitoring Option CANopen Interface Option 2 x Analog input 0 10VDC Option Format 96 x 96 mm 1 4 DIN Installation depth 122 mm DESCRIPTION AND OPERATING MANUAL I ELOTECH Indus...

Page 2: ...ation Instructions 24 Please read this operating manual before starting up carefully Observe the installation and connecting instructions Note Only trained personnel following the regional safety regu...

Page 3: ...erface 5 with heater current monitoring Only with bistable voltage outputs Codes 432 436 437 0 sensor programmable RTD Pt100 DIN 2 or 3 wire Type L Type J Type K 431 4 zones heat only or heating off c...

Page 4: ...roller Control output OUT 1 Zone 1 heating or cooling heating to OUT 4 Zone 4 heating or cooling heating Control output OUT 5 Zone 1 cooling to OUT 8 Zone 4 cooling Alarm Output A1 Alarm 1 Temperature...

Page 5: ...Control output OUT 1 Zone 1 heating or cooling heating to OUT 4 Zone 4 heating or cooling heating Control output OUT 5 Zone 1 cooling to OUT 8 Zone 4 cooling Alarm Output A1 Alarm 1 Temperature or he...

Page 6: ...Control output OUT 1 Zone 1 heating or cooling heating to OUT 4 Zone 4 heating or cooling heating Control output OUT 5 Zone 1 cooling to OUT 8 Zone 4 cooling Alarm Output A1 Alarm 1 Temperature or he...

Page 7: ...controller Control output OUT 1 Zone 1 heating or cooling heating to OUT 4 Zone 4 heating or cooling heating Control output OUT 5 Zone 1 cooling to OUT 8 Zone 4 cooling Alarm Output A1 Alarm 1 Temper...

Page 8: ...controller Control output OUT 1 Zone 1 heating or cooling heating to OUT 4 Zone 4 heating or cooling heating Control output OUT 5 Zone 1 cooling to OUT 8 Zone 4 cooling Alarm Output A1 Alarm 1 Temper...

Page 9: ...nning When the parameter adjustments have been altered but not entered the display will flash bright dark E Confirmation and storage of the pre selected values The display will show a light chain as a...

Page 10: ...e high temperature X 0 5 W SP temperature o k low temperature X 0 5 W SP Zone Zone Zone Zone 1 2 3 4 The displayed dec point shows the heating or cooling on off off off actual situation of the control...

Page 11: ...ing level After either pressing the E key for approx 1 second or waiting for a period of approx 30 seconds the unit will automatically return to the operating level display of process value and setpoi...

Page 12: ...usted and displayed relative to the setpoint deviation alarm as an absolute value LED Switching behaviour Configuration LED Switching behaviour Configuration off on 1 off on 2 8 on off 4 on off 5 9 se...

Page 13: ...ameter Co A1 to number 8 or 9 Heater current monitoring via relay A2 Program parameter Co A2 to number 8 or 9 The heater current to be monitored has to be programed as an absolute value into the opera...

Page 14: ...temperature indications Display indication in this case Comparable with temperature too high But there is no special indication via tendency or alarm status display Display C 0 2 Er Cu PROCESS PROCESS...

Page 15: ...Gateway 8n2 8 data none 2 stopbit bAud Baud rate OFF 0 3 9 6 kBaud The baud rate denotes the transmission rate at which one bit is transmitted InterBus S Gateway 9 6 kBaud Details see sep interface de...

Page 16: ...S 32 2912 F If the Sensor selection is changed the following parameters will be set as follows and need to be re adjusted Setpoint 1 setpoint 2 SP Lo Process value offset OFF Lower setpoint limitatio...

Page 17: ...ults in a slower more regular heating period For this purpose the bistable voltage output must be taken that actuates SSR relays If the softstart is active the controllers autotune function can t oper...

Page 18: ...sensor break was 100 if the controller is working along a setpoint ramp if the control deviation was more than 0 25 of the total range at the time of sensor break if th prop band P xp 0 if the soft st...

Page 19: ...i output ratio limit 0 100 ex works 100 cooling 1 P heating OFF 0 1 100 0 ex works 3 0 prop band P If 1 P OFF control action on off without feedback next parameter 1 Sd 1 d heating OFF 1 200 secs ex w...

Page 20: ...utputs is not possible 2 P cooling OFF 0 1 100 0 ex works 3 0 prop band P If 2 P OFF control action on off without feedback next parameter 2 Sd 2 d cooling OFF 1 200 secs ex works 30 rate D 2 J coolin...

Page 21: ...n The tuning algorithm can be activated at any time by selecting the OPT on and pressing the E key Zone display During self tuning OPt is shown in the display alternating with the setpoint value Tende...

Page 22: ...d setpoint If the ramp is active the corresponding LED lights up on the faceplate The ramp can be activated for both setpoint1 and setpoint2 By programming the second setpoint accordingly a setpoint p...

Page 23: ...ested according to 2004 108 EC EN 61326 1 industrial areas Electr safety EN 61010 1 Power supply Standard 230 V AC 10 48 62 Hz appr 10VA Connections Screw terminals Protection mode IP 20 DIN 40050 Ins...

Page 24: ...in control panels The controller must be installed so that it is protected against impermissible humidity and severe contamination In addition make sure that the permitted ambient temperature is not e...

Reviews: