48
6.4.1 Communication Address
Each Power meter in a communication system must have its own
unique address.
Because the
ElNet Pico
Energy Powermeter
works on
MODBUS, the available addresses are - from ‘1’ to ‘247’.
6.4.2 Baud Rate
The Baud Rate is the communication speed in Bits per second
(BPS) that the
ElNet Pico
Energy Powermeter
communicates
with
the
PC. The better the communication line Quality, the faster
the communications may be.
If the communication line is routed through a “noisy”
environment, it may be necessary to decrease the Baud Rate.
Available Baud Rates for the
ElNet Pico
Powermeter:
300
bps
600
bps
1200
bps
2400
bps
4800
bps
9600
bps
19200
bps
38400
bps
6.4.3 Parity
The choices of parity are either NONE or EVEN (see Section
6.1.1 for description of Parity).