Safety Relay

English

12. Technical Data

Supply voltage

  Low voltage: 

U

E

 

24 V AC/DC ±10 %

  

I

E

  

85 mA

  

I

max

 

180mA (100ms)

  Input power: 

P

E-max

  3 W 24 V DC

  

P

E-max

  3 VA 24 V AC

  Ensuring low 

  voltage (external): 

125mA Medium acti ng fuse

   

125mA Flink can be used 

   

alternati vely

Terminal resistance oft  the sensor

  nominal value 

R

nom

 

     8,2 kΩ

  upper switching point  R

AO

 

> 12,0 kΩ

  lower switching point  R

AU

 

<   5,0 kΩ

Safety relay

Nominal current DC   

DC-13 / 24 V / 2 A

  Nominal current AC 

 

AC-15 / 30 V / 2 A

  Mechanical life-ti me   

>10

6

  actuati ons

Saft ey Relay

  Fuse type 

  

M 2 A 5 x 20 glass tube*

Safety relay switching ti mes

  Switching off  delay 

 

< 12 ms

        

(response ti me)

  

  Turn-off  ti me 

  

500 ms (ELMON relay 32-242)

   

 

100 ms (ELMON relay 32-242 K)

   

 

(Power on 700ms)

Assembly  

Plug-in socket to 35 mm DIN snap-on rail

Housing 

 

11 pol. DIN plug-in socket housing

   

 

with plug-in socket for 35 mm assembly rail

Dimensions 

(HxWxD)

 Housing  

82 x 38 x   84 mm

  Housing incl. plug-in socket 

82 x 38 x 110 mm

Protecti on class 

 

IP20

Weight  

225 g

Temperature range

 

 

-25°C to +55°C

Connecti on terminals

  ti ghtening torque   

 

0,5 Nm

Connecti on cable cross-secti on 

single- or fi ne-stranded cable 0,75-1,5 mm

2

Certi fi cati ons

   

EN ISO 13849-1:2015

   

Categorie 3 PL e

   

MTTFd 180 years, DC 90%

  Electronics  

MTTFd 3757 years, DC 90 %

  Electromechanics 

B10d 1000000 / MTTFd 190 years (Nop 52560)

All voltages connected to the switching unit must be safely isolated!

*Not included in the scope of delivery

84

82

38

26

Summary of Contents for 32-242

Page 1: ...al G ltigkeit siehe letzte Seite ELMON relay 32 242 Sicherheitsschaltger t Operating Manual see last page for validity ELMON relay 32 242 Safety Relay Manuel d utilisation Validit voir la derni re pag...

Page 2: ...al mounting 17 8 Electrical connection 18 8 1 Supply voltage 18 8 2 Sensor connection 18 8 3 Connecting several sensors per sensor circuit 18 8 4 Connecting control circuits 19 9 Commissioning and per...

Page 3: ...ut fail The electrical engineering and professional society safety rules are to be observed When working on the relay it must be disconnected from the power supply tested for zero potential and secure...

Page 4: ...tate of the sensor and the operating voltage supplied are shown by LEDs In the event of a fault alarm all safety outputs are inactive The unit can be used in a household environment as well as an indu...

Page 5: ...or activated on Sensor circuit broken flashes rapidly Fault self lock flashes slowly 5 Verwendungsbeispiele Circuit diagram in zero potential state Sensor not activated ELMON relay 32 242 24 V DC 0 V...

Page 6: ...ON relay 32 242 Safety Relay English If there is no fault alarm the operating state is shown via the LED Power on When signalling a fault alarm the number of pulses emitted indicates the nature of the...

Page 7: ...purpose the individual sensors are connec ted in series according to figure 1 Safety edges SENTIR edge Up to five SENTIR edge may be connected in series The maximum total length oft the SENTIR edge sh...

Page 8: ...can be isolated with the aid of the LED If the fault is not in the wiring the functioning of the electronics may be checked by fitting an 8 2 k resistance to the annunciator input on the relay If the...

Page 9: ...12 ms response time Turn off time 500 ms ELMON relay 32 242 100 ms ELMON relay 32 242 K Power on 700ms Assembly Plug in socket to 35 mm DIN snap on rail Housing 11 pol DIN plug in socket housing with...

Page 10: ...claration of conformity ELMON relay 32 302 ELMON relay 32 312 ELMON relay 32 242 ELMON relay 32 332 ELMON relay 32 302 ELMON relay 32 312 ELMON relay 32 242 ELMON relay 32 332 ELMON relay 32 302 ELMON...

Reviews: